Panasonic KW1M Eco-Power METER User Manual page 22

Table of Contents

Advertisement

Unit for pulse output setting mode
Mode defines unit used for pulse output. It defines the unit of integrated electric power for
1-pulse output.
・Select from 0.001/0.01/0.1/1/10/100kWh /AL-P/AL-C/AL-S/Cnt.
*"AL-S" and "Cnt" are only for AKW1111.
When one of the "0.001/0.01/0.1/1/10/100" [kWh] is set, one pulse is output at reaching the setting
value.
When "AL-P" is set, alarm is output at the time when instantaneous electric power is over the setting
value.
When "AL-C" is set, alarm is output at the time when current is over the setting value.
When "AL-S" is set, alarm is output at the time when current is under the setting value and it passes
the setting time.
When "Cnt" is set, it output at the time when count value reaches preset value set by preset value
setting mode.
Power alarm setting mode
Mode defines instantaneous electric power used for alarm output.
・It is set the range of 0.00 to 9999.99kW.
*This mode is only when " AL-P " is selected on unit for pulse output setting mode.
Current alarm setting mode
Mode defines the ratio of current used for alarm output. (Ratio for the rated current)
・It is set the range of 1.0 to 100.0%.
*This mode is only when "AL-C" is selected on unit for pulse output setting mode.
Stand-by alarm setting mode 1
Mode defines the ratio of current used for threshold value to judge stand-by power.
(Ratio for the rated current)
・It is set the range of 1.0~100.0%.
*This mode is only when "AL-S" is selected on unit for pulse output setting mode.
Stand-by alarm setting mode 2
Mode defines the time used for threshold value to judge stand-by power.
・It is set the range of 0 to 9999min.
When "0" is set, alarm is always output at the time when judging the stand-by power.
When "1 to 9999" is set, alarm is output at the time when passing the setting time with the stand-by
power.
The alarm can be reset by pressing <SET> with the instantaneous electric power display. After reset
the alarm, start to monitor the stand-by power again.
*This mode is only when "AL-S" is selected on unit for pulse output setting mode.
Preset value setting mode
Mode defines count value used for output.
・It is set the range of 0(0.000) to 999999(999.999).
*The range differs according to the pre-scale set by pre-scale setting mode.
*This mode is only when "Cnt" is selected on unit for pulse output setting mode.
Electricity charge setting mode
Mode defines electricity charge ratio used as a standard per 1kWh.
・It can be set the range of 0.00 to 99.99 /1kWh. (Initial 10.00)
Conversion factor setting mode
Mode defines conversion factor of carbon dioxide used as a standard per 1kWh.
・It can be set the range of 0.000~9.999/1kWh. (Initial 0.410)
PL-P
AL-P
AL-C
*only AKW1111
AL-S
*only AKW1111
AL-S
*only AKW1111
Cnt
RATE
CO2
14
KW1M Eco-POWER METER

Advertisement

Table of Contents
loading

This manual is also suitable for:

Akw1111Akw1110

Table of Contents