IEEE 1613 (C37.90.x) EMC Immunity Type Tests
Note
The RUGGEDCOM RS8000T meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports.
IEEE Test
C37.90.3
C37.90.2
C37.90.1
C37.90
Environmental Type Tests
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
Test
IEEE 1613
Clause
9
8
7
6
Test
Cold Temperature
Dry Heat
Humidity (Damp
Heat, Cyclic)
6.2 EMC and Environmental Type Tests
Description
AC Power
ports
Description
ESD
Enclosure Contact
Enclosure Air
Radiated RFI
Enclosure ports
Fast
Signal ports
Transient
DC Power ports
AC Power ports
Earth ground ports
Oscillatory
Signal ports
DC Power ports
AC Power ports
HV Impulse
Signal ports
DC Power ports
AC Power ports
Dielectric
Signal ports
Strength
DC Power ports
AC Power ports
Description
Test Ad
Test Bd
Test Db
Vibration
Shock
Certification
Test Levels
5 kV
Test Levels
±8 kV
±15 kV
35 V/m
±4 kV @ 2.5 kHz
±4 kV
±4 kV
±4 kV
2.5 kV common
mode @ 1MHz
2.5 kV common and
differential mode @ 1MHz
2.5 kV common and
differential mode @ 1MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kVAC (Failsafe Relay)
1.5 kVDC
2 kVAC
Test Levels
Severity Levels
-40 °C (-40
°F), 16 Hours
85 °C (185
°F), 16 Hours
95% (non-
condensing), 55 °C
(131 °F), 6 cycles
2 g @ 10-150 Hz
30 g @ 11 ms
Severity
Levels
 
 
 
 
Class 2
Class 2
29