Checklists For The Versasafe System; B-1.1 Planning - Emerson PACSystems VersaSafe IC220SDL963 User Manual

Enhanced safety logic module, safe output 24vdc, 8 points
Table of Contents

Advertisement

User Manual
GFK-2843A
B-1

Checklists for the VersaSafe system

B-1.1
Planning
Checklist for planning the use of the VersaSafe system
Equipment identification
Author
Remark
No
Requirement (mandatory)
.
1
Has a hazard and risk analysis been carried out for the system/machine?
2
Has the corresponding safety integrity level (SIL, SIL CL, Cat., PL) been
derived from the hazard and risk analysis?
3
Does the VersaSafe system meet the required safety integrity level?
4
Has the current IC220SDL963 user manual been used as the basis for
planning?
5
Has the voltage supply been planned according to the specifications for
the protective extra-low voltage in accordance with PELV?
6
Have safety distances that must be observed been calculated according
to the response and delay times implemented?
7
Has the required shutdown time for the safety function t
the machine/system design been determined?
8
Can the planned application be implemented with the configuration
options (e.g., by using functional blocks)?
9
Does the planned use correspond to the intended use of the system?
10 Has the technical data of the VersaSafe system been observed?
11 Has it been ensured that in an overall system consisting of the VersaSafe
system and any higher-level PROFIsafe system, the addresses (address
within the VersaSafe system and F-Address of the PROFIsafe system) are
unique?
12 Within a VersaSafe system, is each island number only assigned once?
(During
13 Is the application stop (OFF, STOP, emergency stop, triggering of safety
simultaneous use of IC220SDL963 and IC220SDL963, the island number
equipment) implemented according to EN 60204?
of the
14 When planning the safety functions, has the VersaConf Safety software
IC220SDL963 system must be >= 8.)
tool been used to determine whether the memory space is sufficient for
the size of the safety logic?
15 Has it been ensured that any person intentionally starting hazardous
movements has a direct view of the danger zone?
16 Are there fewer than 6 serial chains between the logic modules within a
safety function?
No
Requirement (optional)
.
17 Are all measures that are based on applicable standards planned?
18 Have the VersaPoint specifications (e.g., cabling, power supply) been
observed?
checklists
Date
Test engineer
Yes
resulting from
SF
Yes No
Appendix B
Jan 2020
Remark
Revision:
t
:
SF
Remark
95