The Serial Port page displays information about the
RS232 serial port, which enables data transfers. If an
external modem is connected to the serial port, modem
information also displays.
NOTE: The Serial Port page display may vary, in
accordance with controller configuration.
See
2-15. If a modem is connected to the
Figure
controller, Modem displays, as illustrated.
Figure 2-15. Serial Port Page. If modem is not
connected, RS232 displays in place of Modem.
See
Figure
2-16. When the controller can accept a data
transfer, Modem Ready displays, as illustrated.
Figure 2-16. Serial Port Page—Modem Ready
Program File Information Page
Figure 2-17. Program File Information Page
The Program File Information page displays the following
controller information.
Controller model unit
Program file name
Program PN
Program version
Owner's Manual for Mobile Generator
About Page
010426
The About page displays various general information about
the unit and controller, as illustrated.

Maintenance Alarms

010427
Maintenance alarms indicate a regular-maintenance
service interval is expired. To resolve the condition,
perform
the
corresponding service interval.
To re-set a service interval:
1. Display the Engine page.
2. Scroll (▲ or ▼) until the appropriate service inter-
val is highlighted.
NOTE: The expired interval displays on the Alarm page.
3. Press and hold the Engine STOP/RESET Mode
010428
button until ###* hr service changes to 0 hr service.
*A number displays. The value varies according to
what service interval is highlighted.
General Information
Figure 2-18. About Page