Configurations
4
Modbus configuration parameters
4 Configurations
4.1 Modbus configuration parameters
4.2 Modbus registers
12 | 26
Siemens
The sensor is a Modbus (RS485) slave device, configurable via a Modbus master.
Name
Configurable
Address
Baud rate (bps)
Transmission format
Basic
Parity
Stop bits
Connection
Data
Identity
Cable length
Holding
Name
Register No.
257
PM2.5 value
258
PM10 value
260
Sensor working status
296
Software version
297
Software version
298
Software version
764
Modbus address
765
Baud rate
766
Transmission format (start
bit – data bits – parity –
stop bit)
768
Bus configuration
command
Range / Enumeration
1...247
1 = 9600 / 2 = 19200/
3 = 38400 / 4 = 57600
0 = 1-8-E-1 / 1 = 1-8-O-1 /
2 = 1-8-N-1 / 3 = 1-8-N-2
Even / Odd / No
1 / 2
<= 32pcs/line
8 bits (0-255)
Slave
<600m
Description
Default
Range: 0...500
Range: 0...500
0: Normal;
1: Replace sensor
module;
2: Communication
error
Major version
Minor version
Build version
1...247
1
1= 9600bps / 2 =
2
19200bps / 3 =
38400bps / 4 =
57600bps
0 = 1-8-E-1 / 1 = 1-
0
8-O-1 / 2 = 1-8-N-1
/ 3 = 1-8-N-2
0 = Ready / 1 =
0
Load / 2 = Discard
Default
1
19200
0
Even
1
R/W
R
R
R
R
R
R
R / W
R / W
R / W
R / W
A6V11160936_en--_a
2017-12-01