This installation manual contains only the description of how to install the Drain pump PAC-KE07DM-E. For information about how to wire and
how to install air conditioning units, see the installation manual for them.
For your safety, first be sure to read " 1 Safety Precautions " described below thoroughly and then install the Drain pump PAC-KE07DM-E
correctly.
1 Safety Precautions
The following two symbols are used to denote dangers that may be caused by incorrect use and their degree:
. WARNING
This symbol denotes what could lead to serious injury or death if your misuse the PAC-KE07DM-E.
. CAUTION
This symbol denotes what could lead to a personal injury or damage to your property if you misuse the PAC-KE07DM-E.
After reading this installation manual, keep it in a place where the final user can see it anytime he or she wants to it.
When someone moves, repairs or uses the PAC-KE07DM-E, make sure that this manual is forwarded to the final user.
Always have the unit installed by Authorized Mitsubishi
Representative or similar professional.
Improper installation by the user could result in problems such as
water leakage, electric shock or fire.
Always use the designated cables and connect them properly.
When connecting the terminals, make sure that external forces
from the cable is not being conveyed to the terminal and then
tighten it securely.
Improper or loose connections could cause excessive heat or fire.
Only use Mitsubishi-approved accessories, such as an air
cleaner, humidifier or electric heater.
Always have such accessories installed by an Authorized Mitsubishi
Representative or similar professional. Improper installation by the
user may result in water leakage, electric shock or fire.
PRECAUTIONS BEFORE INSTALLATION
Never use for special applications such as storing food, plants,
precision equipment or art.
The quality of these items may deteriorate.
Never use the unit in special environments.
Special environments with high concentrations of oil, steam or sulfu-
ric gases will reduce the performance of the air condition and cause
its parts to deteriorate.
Never install the unit where run-off could result in damage.
If the humidity in the room exceeds 80% or if the drain becomes
clogged, water may drain off of the indoor unit. When the unit is used
for heating, there may be drainage from the outdoor unit. If required,
provide collector drain for the outdoor unit.
PRECAUTIONS BEFORE REMOVE AND ELECTRIC WORK
Route wiring so that there is no tension.
Tension could cause the wire to break and this could result in exces-
sive heat or fire.
Dispose of packing materials properly.
PRECAUTIONS BEFORE TEST RUN
Never touch the switch with wet hands.
Electric shock could occur.
Never operate the air conditioner with the panel or guard
removed.
The hand could come in contact with rotating, hot or high-pressure
components. They could cause electrical shock or entanglement.
PAC-KE07DM-E
CAUTION
WARNING
Install the unit according to this Installation Manual.
If the unit is installed improperly, water leakage, electric shock or fire
may result.
Have all electric work performed by a properly licensed electri-
cian. Electric work should be performed in strict adherence to
procedures to this Installation Manual. Always provide a dedi-
cated power supply.
If the capacity of the power supply is inadequate, it could result in
problems such electric shock or fire.
Never modify the unit and always have repairs performed by an
Authorized Mitsubishi Representative.
Improper repair could result in problems such water leakage, electric
shock or fire.
Always provide adequate signal noise protection when
installing in facilities such as hospitals and communication sta-
tions.
Equipment at these facilities, such as inverters, in-house generators,
high-frequency medical equipment, two-way communication equip-
ment, may cause the air conditioner to operate improperly.
Conversely, the signal noise from the air conditioner may affect the
operation of medical equipment and two-way communication equip-
ment and this could interfere with the medical treatment being given
a patient or cause disturbances or interference in video broadcasting
equipment.
Use care when transporting the unit.
•Always use two or more people for lifting a product weight 20 kg. or
more.
•Some products are packaged with plastic wrapping bands. Never
use these for lifting or transporting the product.
•Never touch the fins on the heat exchanger. They are sharp and
could cause cuts.
•Never allow children to play with the plastic bags used for packag-
ing. Always tear them up when disposing. A child could suffocate
in these bags.
Never operate the air conditioner with the air filter removed.
Particles will enter into the air conditioner and cause damage.
Never turn off the power supply immediately after stopping the
unit.
Wait five minutes or more before turning off the power supply.
Turning off the power supply before that time could result in water
leakage or damage.

Advertisement

loading

Summary of Contents for Mitsubishi PAC-KE07DM-E

  • Page 1 This installation manual contains only the description of how to install the Drain pump PAC-KE07DM-E. For information about how to wire and how to install air conditioning units, see the installation manual for them. For your safety, first be sure to read “ 1 Safety Precautions “ described below thoroughly and then install the Drain pump PAC-KE07DM-E correctly.
  • Page 2 2 Confirming the Supplied Parts 1. Model names and applicable models Model name Applicable types SEZ-M25DA(L), SEZ-M35DA(L), SEZ-M50DA(L) SEZ-M60DA(L), SEZ-M71DA(L) PAC-KE07DM-E PEFY-P15VMS1L-E, PEFY-P20VMS1L-E PEFY-P25VMS1L-E, PEFY-P32VMS1L-E PEFY-P40VMS1L-E, PEFY-P50VMS1L-E PEFY-P63VMS1L-E 2. Provided parts Check that the packet includes the following parts in addition to this installation manual.
  • Page 3 3 Installing the Drain Pump 3-1 Installing the Drain Pump Hook the 2ATTCHMENT over the mounting bracket on the unit. (1) Unscrew the (a)screw on the unit cover, hook the 2ATTACHMENT over the mounting bracket on the unit, and screw it on to the unit with the (a)screw. (Fig. 1) 2ATTACHMENT Cover Fig.
  • Page 4: Installing Drain Hose

    3-2 Installing DRAIN HOSE 1 (1) Connect each end of 3DRAIN HOSE 1 to the drain port on the unit and on the drain pump. (Fig. 5) Insert the hose all the way to the end of the ports. Do not use any adhesive. 6HOSE BAND (2) Secure the hose with 6HOSE BANDs at both ends of the hose.
  • Page 5 (3) Remove the short-circuit connector from CN4F on the control board (white, 4P). (Fig. 8) Drain pump wires (2 wires) Short-circuit connector (4) Route the two drain pump wires behind the CON- TROL BOX and into the CONTROL BOX. Lift the CONTROL BOX in the direction of the arrow (d) to allow the wires through.
  • Page 6: Drain Piping Work

    4 Drain piping work • Ensure that the drain piping is downward (pitch of more than 1/100) to the outdoor (discharge) side. Do not provide any trap or irregularity on the way. • Ensure that any cross-wise drain piping is less than 20 m (excluding the difference of elevation). If the drain piping is long, provide metal braces to prevent it from waving.
  • Page 7 5 Confirming drain discharge Make sure that the drain-up mechanism operates normally for discharge and that there is no water leakage from the connections. • Be sure to confirm the above in a period of heating operation. • Be sure to confirm the above before ceiling work is done in the case of a new construction.