Flueing guidelines

Combustion air provided to the system should not be taken from any area that may produce a
negative pressure (i.e exhaust fans, powered ventilation fans etc.). Room combustion air requires
compliant louvres in a plant room door or wall, refer AS/NZS 5601.1:2013 for more information.
For appliance and user safety NEVER use Rinnai flue components with other manufacturer's water
heaters.
Maximum flue length
Header
Main flue pipe into which other flue components connect
Stocked ex-Auckland
Header size
Ø110 mm header
Ø110 mm flue
Horiz. termination ONLY
Please note: For every 90° bend used, subtract 3 m from the lengths below
Number of
Maximum flue length
water heaters
2
45 m
3
45 m
4
20 m
5
6
7
8
9
10
11
12
UV protection
Where appropriate, all components must be protected from UV. The horizontal terminals are UV
resistant. The vertical terminals are supplied with a stainless outer for UV protection. Anything else
exposed to UV should be painted with a system suitable for polypropylene.
6 | Rinnai INFINITY N56kWi common flue installation guide 13088-B 04-20
Flue length
Distance from the end of the header to the flue termination
The maximum flue length starts at the end of the header
system.
Ø110 mm header
Ø160 mm flue
Horiz. and vertical termination Horiz. and vertical termination
45 m
45 m
45 m
45 m
45 m
21 m
Not in this manual,
contact Rinnai
Indent order: 16 weeks
Header size
Ø160 mm header
Ø160 mm flue
45 m
45 m
27 m
27 m
12 m