Install the motion sensor
Place the connector under the panel and install it to the panel with careful attention to the direction of the
motion sensor.
CAUTION: Connect the connectors before installing the motion sensor.
In case of connecting after the motion sensor has been installed, it will be necessary to remove the
panel.
Wiring connection in the control box
Connect the wiring from the motion sensor (attached to the indoor unit, color of the wiring: white, red
and black, connector: 3P, white) to the attached wiring to the motion sensor kit.
Fix the wiring with clips (6 places).
Connect CnG connector (4P, blue) to the PCB.
Connect CnV2 connector (4P, black) to the PCB.
CnG connector
(4P, blue)
Clip
Setting the motion sensor
The motion sensor will not function if it is only installed.
Set the function of the motion sensor by the wired or wireless remote control. Refer to the manual
instruction of each remote control for the setting procedure.
Note: It is not possible to set by the following remote control models or older.
Wired:RC-EX1A, RC-E5, RCH-E3
Wireless: RCN-E1R
CnV2 connector
(4P, black)
Control box
Attached wiring to the
motion sensor kit
146
-
Connect the wiring
Attached wiring to the
(3P, white)
indoor unit
Connector (3P, white)
Clips
Wiring from the
motion sensor
-
'19 • KT-T-310D