Inspection procedures corresponding to detail of trouble

Sensor error

Is connector connection good?
YES
Is sensor resistance value good?
YES
Replace PCB.
◆ Discharge pipe sensor temperature characteristics
Temperature (˚C)
Resistance (kΩ)
0
5
10
15
20
25
30
35
40
45
50
55
60
65
Indoor fan motor error
Is connector connection good?
YES
* Disconnect the fan motor
connector, then investigate
the DC fan motor and indoor
unit circuit board separately.
Is the output of the indoor unit's
printed circuit board normal?
YES
Normal
NO
Correct connection.
NO
Temperature (˚C)
Resistance (kΩ)
164
70
127
75
99
80
78
85
62
90
50
95
40
100
32
105
26
110
21
115
17
120
14
125
12
130
10
135
NO
Correct connector connection
Is DC fan motor resistance value good?
NO
Replace indoor PCB
Replace sensor.
◆ Sensor temperature characteristics
(Room temp., indoor unit heat exchanger
temp., outdoor unit heat exchanger
temp., outdoor air temp.)
8.7
7.3
6.2
5.3
(Broken wire)
4.5
3.9
3.3
2.9
2.5
2.2
1.9
(Shortcircuit)
1.6
1.4
1.3
NO
YES
Replace indoor fan motor
Notes (1) See pages 208, 209 for the DC fan motor and indoor unit
(2) After making sure the DC fan motor and indoor unit circuit
206
-
-
[Broken sensor wire,
connector poor connection]
30
25
20
15
10
5
–10
0
10
20
30
Temperature (˚C)
[Defective fan motor, connector
poor connection, defective PCB]
circuit board check procedure.
board are normal, connect the connectors and confirm that
the fan motor is turning.
(If power is turned on while one or the other is broken down,
it could cause the other to break down also.)