1. Self-Diagnostics Function Table
The outdoor unit maintenance remote controller can be used to check the alarm display.
The number of times that LED 1 and 2 blink on the outdoor unit control PCB can be used to check the alarm
display. (Refer to "Checking the LED 1 and 2 Alarm Display on the Outdoor Unit Control PCB.")
Remote
controller
display
E06
Trouble receiving the signal from the indoor unit at the outdoor unit
E12
Automatic address setting start-prohibit
E15
Automatic address setting alarm (too few units)
E16
Automatic address setting alarm (too many units)
E20
No indoor units when automatic address setting was started
E24
Trouble receiving the signal from the outdoor unit at the relay control unit
E25
Trouble with the outdoor unit address setting
E29
Trouble receiving the signal from the relay control unit at the outdoor unit
E30
Trouble with sending the outdoor unit serial signal
F04
Compressor 1 – Discharge temperature sensor trouble
F07
Outdoor coil liquid temperature sensor trouble
F08
Outside air temperature sensor trouble
F12
Compressor inlet temperature sensor trouble
F16
High-pressure sensor trouble
F31
Outdoor unit non-volatile memory (EEPROM) trouble
H03
Compressor 1 – CT sensor disconnected or short circuit
H31
Compressor HIC alarm (Also check the description of alarm P29.)
L05
Duplicated indoor unit priority (priority indoor unit)
L06
Duplicated indoor unit priority (non-priority indoor unit) and outdoor unit
L10
Outdoor unit capacity not set.
L17
Outdoor unit type mismatch
P03
Compressor 1 – Abnormal discharge temperature
5
P13
Out of step detected
P14
O
2
P16
DCCT or ACCT overcurrent at less than 80 Hz
Outdoor unit fan trouble (IPM damage, overcurrent, inverter trouble, DC fan lock, Hall IC missing
P22
phase)
Missing-phase/reverse-phase in the compressor wiring, Compressor start-up
P29
failure (Overcurrent at time of INV compressor starts up, etc.)
sensor activated.
Self-Diagnostics Function Table
Cause
5-4
Mini VRF SYSTEM
(TD)
(C1)
(TO)
(TS)
(HPS)