The pulse modulating circuits are mounted to both
indoor and outdoor units. Therefore, diagnose troubles
according to the diagnosis procedure as described
below. (Refer to the check points in servicing written on
the wiring diagrams attached to the indoor/outdoor
units.)
Table 10-1
No.
Troubleshooting Procedure
1

First Confirmation

2
3
of Indoor Unit
4
5
Every Symptom
6
How to Check Simply the Main Parts
10-1. First Confirmation
10-1-1. Confirmation of power supply
Confirm that the power breaker operates (ON)
normally.
10. HOW TO DIAGNOSE THE TROUBLE
Page
50
51
52
53
56
63
Discharging position
(Discharging period
10 seconds or more)
NOTE:
A large-capacity electrolytic capacitor is used in the
outdoor unit controller (inverter). Therefore, if the power
supply is turned off, charge (charging voltage DC280V)
remains and discharging takes a lot of time. After
turning off the power source, if touching the charging
section before discharging, an electrical shock may be
caused. Discharge the electrolytic capacitor completely
by using soldering iron, etc.
<Discharging method>
(1) Remove the inverter cover (plating) by opening
four mounting claws.
(2) As shown below, connect the discharge resistance
(approx. 100Ω40W) or plug of the soldering iron to
voltage between + - terminals of the C12
("CAUTION HIGH VOLTAGE" is indicated.)
electrolytic capacitor (500µF/400V) on P.C. board,
and then perform discharging.
Plug of
soldering
iron
Fig. 10-1
10-1-2. Confirmation of power voltage
Confirm that power voltage is AC 220-240 V ± 10%. If
power voltage is not in this range, the unit may not
operate normally.
- 50 -
FILE NO. SVM-07018
Inverter cover
PC board
(Soldered surface)