Stopping The Engine - Briggs & Stratton PowerBOSS 030249 Operator's Manual

5500w
Hide thumbs Also See for PowerBOSS 030249:
Table of Contents

Advertisement

Available languages

Available languages

PowerBOSS™

Stopping the Engine

1.
Turn OFF and unplug all electrical loads from
generator panel receptacles. NEVER start or stop engine
with electrical devices plugged in and turned ON.
2.
Let engine run at no-load for several minutes to
stabilize internal temperatures of engine and generator.
3.
Turn engine off according to instructions given in the
engine operator's manual.
4.
Move fuel valve to "Off" position.
GENERATOR ADAPTER
CORD SET
The generator is equipped with a 25' generator adapter
cord set designed for a 240 Volt, 30 Amp grounded neutral
circuit (Figure 5).
Figure 5 — Generator Adapter Cord Set
The maximum load on each outlet is 20 Amps.The
maximum total load on both yellow wire outlets or both
black wire outlets is 30 Amps.
NOTE: Follow all safety precautions when connecting any
extension cord or device to the generator.
RECEPTACLES
CAUTION
Receptacles may be marked with rating value greater
than generator output capacity.
• NEVER attempt to power a device requiring more amperage
than generator or receptacle can supply.
• DO NOT overload the generator. See "Don't Overload
Generator".
5500W Portable Generator
120/240 Volt AC, 30 Amp, Locking
Receptacle
Use a NEMA L14–30 plug with this receptacle. Connect a
4–wire cord set rated for 250 Volt AC loads at 30 Amps (or
greater) (Figure 6).You can use the same 4–wire cord if you
plan to run a 120 Volt load.
Figure 6 — 120/240 Volt AC, 30 Amp Receptacle
NEMA L14-30
This receptacle powers 120/240 Volt AC, 60 Hz, single
phase loads requiring up to 5,500 watts of power (5.5 kW)
at 22.9 Amps for 120 Volts or 240 Volts.The outlet is
protected by a push–to–reset circuit breaker.
120 Volt AC, 20 Amp, Duplex
Receptacle
Each duplex receptacle (Figure 7) is protected against
overload by a push–to–reset circuit breaker.
Figure 7 — 120 Volt, 20 Amp Duplex Receptacle
Use each receptacle to operate 120 Volt AC, single–phase,
60 Hz electrical loads requiring up to 2,400 watts (2.4 kW)
at 20 Amps of current. Use cord sets that are rated for
125 Volt AC loads at 20 Amps (or greater).
10
4-Wire Cord Set
240V
120V
120V
Y (Hot)
Ground (Green)
OPERATION
W (Neutral)
X (Hot)