Compressor Replacement Procedure

1. Turn OFF the power supply to the refrigeration unit.
2. Remove the mounting plate above the compressor and remove the terminal cover
securing bracket (Clip), and then remove the compressor terminal cover.
Remove all lead wires of R, S, and T phase from the compressor.
Compressor lead wire harness
3. Remove the crankcase heater from the compressor.
Crankcase heater
securing spring
Note: Bundle the lead wires of the compressor and crankcase heater in a position
where they will not be affected by the heat during later pipe brazing operations.
Mounting plate
(Secured by two screws)
Compressor
Terminal cover securing bracket (Clip)
13
Terminal cover
R, S, and T phase terminals
Crankcase heater

Advertisement