OPERATING THEORY

OPERATING THEORY
Chill Loads
Setpoints at -9.9 C
(14.4 F) and Above
Cool w/Mod
Heat
1
1
5
1
Setpoint temperature and controlling mode
setting determine the evaporator fan speed:
Normal Operation :
Chill Loads — High
or low speed fans; Frozen Loads — Low speed
fans or no fans.
2
Vapor injection valve:
Chill, Frozen or Power Limit Mode:
When the cool capacity is 100 percent.
26

MAGNUM+ Operating Mode Function Chart

Frozen Loads
Setpoints at -10 C
(14 F) and Below
Defrost
Cool
Null
1
1
4
Compressor High Temperature
Protection:
temperature exceeds 138 C (280 F).
Condenser fan pulses on and off on a 30
3
second duty cycle to maintain a minimum
condenser temperature:
Chill Loads:
minimum 30 C (86 F) condenser temperature.
Defrost
Evaporator Fans High Speed
Evaporator Fans Low Speed
Evaporator Fans Off
Proportional-integral Derivative (Supply Air) Control
Return Air Sensor Control
Evaporator Coil Sensor Control
Compressor On
Compressor Vapor Injection On (valve energized)
Condenser Fan On
Digital Control Valve Modulating (energized)
Electric Heaters Pulsing or On (energized)
When the compressor discharge
Controller maintains a
Unit Function
1
1
1
2
3
4
5
Frozen Loads:
Controller maintains a
minimum 20 C (68 F) condenser temperature.
4
Digital Control valve modulates: Chill Loads
— whenever the unit is in a Cooling mode;
Power Limit — whenever the unit is in Power
Limit mode.