APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
CCN TABLE NAME: CONF_OPT
PIC6 PATH: Main Menu Configuration Menu Option
LINE
PIC6 DESCRIPTION
1
Auto Restart Option
2
Common Sensor Option
EC Valve Option
3
0 = No, 1= Cont
2 = On/Off, 3 = 4-20 mA
EC Selection
4
0 = Disable, 1 = Surge
2 = Low Load, 3 = Comb
5
ECV Open IGV1 Position
6
ECV Close IGV1 Position
7
ECV Off DT for Low Load
8
ECV On DT for Low Load
9
ECV Low Load DB
10
Head Pres Valve Option
11
Head Pres Delta P 0%
12
Head Pres Delta P 100%
13
Head Pressure Min Output
14
Head Pressure Deadband
15
Tower Fan High set point
16
Refrigerant Leak Option
17
Refrig Leakage Alarm mA
18
Gas Torque Factor
19
Guide Vane/SRD Factor
20
Power Recovery Timeout
21
Customer Alert Option
22
Ice Build Option
23
Ice Build Recycle
Ice Build Termin Source
24
0 = Temp, 1 = Contact, 2 = Both
25
Water Pressure Option
Water Flow Measurement
26
0 = No, 1 = Digital, 2 = Analog
Water Flow Determination
27
0=Sat Temp, 1= Flow Switch
28
Water Flow at 4 mA
29
Water Flow at 20mA
30
Evap Flow Rate Baseline
31
Evap Pres Drop Baseline
32
Cond Flow Rate Baseline
33
Cond Pres Drop Baseline
34
Water Pres Drop @ 20mA
35
Evap Liquid Temp Opt
Evap App Calc Selection
36
Sat Temp = 0, Ref Temp = 1
37
Remote Stop Contact
LEGEND
RW — Read/Write
*Default value is shown only if configurable in this table.
Option
CCN NAME
astart
DISABLE/ENABLE
commsens
DISABLE/ENABLE
hgbp_opt
hgbp_sel
hpop_gv1
hgcl_gv1
hgb_toff
0.5 to 10.0
hgb_ton
0.5 to 10.0
hgbp_ldb
hdpv_opt
DISABLE/ENABLE
hdp_0
hdp_100
hdpv_min
0.0 to 100.0
hdpv_db
tfh_sp
leak_en
DISABLE/ENABLE
exv_opt
gt_fact
0.25 to 3.0
gv_srd_f
0.7 to 1.20
pd_tcfg
cusa_opt
DISABLE/ENABLE
ice_opt
DISABLE/ENABLE
ice_recy
DISABLE/ENABLE
ice_term
wp_opt
DISABLE/ENABLE
wfm_opt
fs_opt
flow4ma
flow20ma
chwf_bas
evpd_bas
cdwf_bas
cdpd_bas
wpd_20ma
evap_ref
DISABLE/ENABLE
evap_ref
rem_stop
DISABLE/ENABLE
57
DEFAULT
RANGE
VALUE*
DISABLE
DISABLE
0 to 3
0
0 to 3
0
0.5 to 10
5.0
1.5 to 20
10.0
4.0
2.0
0.5 to 2.0
1.0
DISABLE
0 to 85.0
25.0
0 to 85.0
50.0
0.0
0 to 10
1
55 to 105
75
DISABLE
4 to 20
20
1
0.95
0 to 60
15
DISABLE
DISABLE
DISABLE
0 to 2
0
DISABLE
0 to 2
0
0 to 1
0
0 to 200
0.00
0 to 200
0.00
0 to 150
0.00
0 to 20
0.00
0 to 150
0.00
0 to 20
0.00
0 to 40
10.00
ENABLE
0/1
1
DISABLE
UNIT
READ/WRITE
RW
RW
RW
RW
%
RW
%
RW
^F
RW
^F
RW
^F
RW
RW
psid
RW
psid
RW
%
RW
°F
RW
RW
RW
RW
°F
RW
RW
min
RW
RW
RW
RW
RW
RW
RW
RW
GPS
RW
GPS
RW
GPS
RW
PSI
RW
PSI
RW
PSI
RW
PSI
RW
RW
RW
RW