Carrier AquaEdge 19DV Controls Operation And Troubleshooting page 53

Two-stage high-efficiency semi-hermetic centrifugal liquid chillers with pic6 controls
Table of Contents

Advertisement

APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
CCN TABLE NAME: MODES
PIC6 PATH: Main Menu  Modes
LINE
PIC6 DESCRIPTION
Normal Shutdown
1
Recycle Shutdown
2
Alarm Shutdown
3
4
Recycle Startup
5
Temperature Ramping
6
Load Ramping
IGV1 Inhibiting
7
Ice Building
8
Ice Build Terminated
9
10
Ice Build Recy Startup
11
Ramp Loading
12
Demand Limit
VFD Rampdown
13
Demand Limit Inhibit
14
Evaporator Frozen
15
16
Condenser Frozen
17
Recycle Shutdown Done
18
NonRecycle Shutdown Done
In Alarm
19
In Override
20
Purge Active
21
22
Comp 1 Run State Val
LEGEND
RO — Read Only
CCN TABLE NAME: SETPOINT
PIC6 PATH: Main Menu  Setpoint
LINE
PIC6 DESCRIPTION
1
Cooling ECW Setpoint
Cooling LCW Setpoint
2
Heating ECDW Setpoint
3
Heating LCDW Setpoint
4
5
Ice Build Setpoint
6
Base Limit Demand
7
EWT Control Option
LEGEND
RW — Read/Write
*Default value is shown only if configurable in this table.
Modes
CCN NAME
shut_nor
shut_rcy
shut_alm
str_rcy
tmp_ramp
ld_ramp
gv1_inh
ice_act
ice_term
ice_rcy
ramp_act
dem_act
vfdrpact
dem_inh
evapfrze
condfrze
rcysh_cm
nrysh_cm
alm_act
over_act
pg_act
cm_stat1
*Default value is shown only if configurable in this table.
Setpoint
CCN NAME
ecw_sp
15.0 to 120.0
lcw_sp
10.0 to 120.0
ecdw_sp
63.0 to 150.0
lcdw_sp
68.0 to 150.0
ice_sp
15.0 to 60.0
dem_base
10.0 to 100.0
EWT_OPT
DISABLE/ENABLE
53
DEFAULT
RANGE
VALUE*
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
NO/YES
DEFAULT
RANGE
VALUE*
60.0
45.0
104.0
113.0
40.0
100.0
DISABLE
UNIT
READ/WRITE
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
Integer
RO
UNIT
READ/WRITE
°F
RW
°F
RW
°F
RW
°F
RW
°F
RW
%
RW
RW