5.2

Interrupts

The AI 4xRTD/TC 4xM12 analog input module supports diagnostic and hardware interrupts.
Diagnostic interrupt
The table below shows the events for which the analog input module returns a diagnostic
interrupt, depending on the parameter assignment.
Table 5- 3
Measure-
ment type
Voltage
Resistance
Thermal
resistor
Thermocou-
ple
Hardware interrupt
The analog input module generates a hardware interrupt with the following events:
• Low limit 1 violated
• High limit 1 violated
• Low limit 2 violated
• High limit 2 violated
Detailed information on the event is available in the hardware interrupt organization block
with the instruction "RALRM" (Read additional interrupt information) and in the STEP 7 online
help.
The start information of the organization block includes information on which channel of the
analog input module triggered the hardware interrupt.
Note
High limit violation of 2 limits
If two limits are violated at the same time, limit 1 is always signaled first, followed by limit 2.
Analog input module AI 4xRTD/TC 4xM12 (6ES7144-5KD50-0BA0)
Equipment Manual, 08/2020, A5E48753535-AA
Diagnostic interrupts
Wire
High limit
break
violated
-
x
x
x
x
x
x
x
Diagnostics
Low limit
Error
violated
signment
x
x
-
x
x
x
x
x
Interrupts/diagnostics alarms
5.2 Interrupts
Parame-
Reference
Hardware
ter as-
channel
interrupt
error
lost
error
x
-
x
-
x
-
x
x
x
x
x
x
37

Advertisement

Table of Contents
loading

This manual is also suitable for:

6es7144-5kd50-0ba0

Table of Contents