Delivery; Storage; Storage Of The Ups; Storage Of Battery - ABB TLE Scalable Series Installation Manual

40 to 150 kva ul s1
Table of Contents

Advertisement

15/54

4.2 Delivery

When delivered, inspect the package integrity and the physical conditions of the cabinets carefully.
In case of any damage sustained during transport, immediately inform the carrier and contact your local ABB
Service Center.
A detailed report of the damage is necessary for any insurance claim.
Note!
A damaged UPS must never be installed or connected to Utility or Battery!

4.3 Storage

4.3.1 Storage of the UPS

It is advisable to store the UPS in its original package in a dry, dust-free room, away from chemical substances,
and with a temperature range not exceeding -13°F (-25°C) to 131°F (55°C).
In case the Battery is included please refer to Section 4.3.2.
Some important functions of the UPS, such as the customized functions, are defined by parameters stored in a
RAM memory.
A small backup Battery located on the Control Unit board supplies the RAM.
If the storage time of the UPS exceeds 1 year, these functions should be verified by an authorized Service Center
before putting the UPS into operation.

4.3.2 Storage of Battery

When the delivery includes a maintenance free Battery, keep in mind that they are subject to self-discharge and
therefore you must recharge the Battery.
The storage time without Battery recharge depends on the temperature of the storage site.
The optimal room temperature for Battery storage is 68°F (20°C) to 77°F (25°C) and shall never exceed the range -
4°F (-20°C) to 104°F (40°C).
Recharge stored maintenance free Battery every:
6 months when the storage temperature is 68°F (20°C)
3 months when the storage temperature is 86°F (30°C)
2 months when the storage temperature is 95°F (35°C)
The equipment is carefully packed for transport and storage so that it is in a
perfect condition when eventually installed.
Never leave an UPS outside the building and do not store the UPS one on top of
the other.
TLE Scalable Series 40 to 150 UL S1
UPS Installation Guide / REV-B