Wiring Of Main Power Supply And Equipment Capacity - Mitsubishi Electric City Multi PUHY-P72TKMU-A Installation Manual

Air-conditioners for building application inverter y-series
Hide thumbs Also See for City Multi PUHY-P72TKMU-A:
Table of Contents

Advertisement

Available languages

Available languages

11.4. Wiring of main power supply and equipment capacity

Schematic Drawing of Wiring (Example)
[Fig. 11.4.1]
T(S)KMU: 3~208-230V
Y(S)KMU: 3~460V
L
, L
, L
1
2
3
~208-230V
L
, L
1
2
A Switch (Breakers for wiring and current leakage)
D Pull box
Thickness of wire for main power supply, on/off capacities
<Power source: 208V / 230V>
Model
Unit combination
PUHY-P72TKMU-A(-BS)
PUHY-P96TKMU-A(-BS)
PUHY-P120TKMU-A(-BS)
PUHY-P144TKMU-A(-BS)
PUHY-P96TKMU-A(-BS)
PUHY-P168TSKMU-A(-BS)
PUHY-P72TKMU-A(-BS)
PUHY-P120TKMU-A(-BS)
PUHY-P192TSKMU-A(-BS)
PUHY-P72TKMU-A(-BS)
PUHY-P120TKMU-A(-BS)
PUHY-P216TSKMU-A(-BS)
PUHY-P96TKMU-A(-BS)
PUHY-P120TKMU-A(-BS)
PUHY-P240TSKMU-A(-BS)
PUHY-P120TKMU-A(-BS)
PUHY-P120TKMU-A(-BS)
Outdoor
PUHY-P264TSKMU-A(-BS)
PUHY-P72TKMU-A(-BS)
unit
PUHY-P72TKMU-A(-BS)
PUHY-P120TKMU-A(-BS)
PUHY-P288TSKMU-A(-BS)
PUHY-P96TKMU-A(-BS)
PUHY-P72TKMU-A(-BS)
PUHY-P120TKMU-A(-BS)
PUHY-P312TSKMU-A(-BS)
PUHY-P120TKMU-A(-BS)
PUHY-P72TKMU-A(-BS)
PUHY-P120TKMU-A(-BS)
PUHY-P336TSKMU-A(-BS)
PUHY-P120TKMU-A(-BS)
PUHY-P96TKMU-A(-BS)
PUHY-P120TKMU-A(-BS)
PUHY-P360TSKMU-A(-BS)
PUHY-P120TKMU-A(-BS)
PUHY-P120TKMU-A(-BS)
B
A
C
Ground
B
A
E
E
Ground
Ground
Ground
B Breakers for current leakage
E Indoor unit
Minimum wire thickness (mm
[AWG]) Switch (A)
2
Main cable Branch
Ground
5.3 [10]
5.3 [10]
8.4 [40]
8.4 [40]
13.3 [6]
13.3 [6]
13.3 [6]
13.3 [6]
8.4 [40]
8.4 [40]
5.3 [10]
5.3 [10]
13.3 [6]
13.3 [6]
5.3 [10]
5.3 [10]
13.3 [6]
13.3 [6]
8.4 [40]
8.4 [40]
13.3 [6]
13.3 [6]
13.3 [6]
13.3 [6]
13.3 [6]
13.3 [6]
5.3 [10]
5.3 [10]
5.3 [10]
5.3 [10]
13.3 [6]
13.3 [6]
8.4 [40]
8.4 [40]
5.3 [10]
5.3 [10]
13.3 [6]
13.3 [6]
13.3 [6]
13.3 [6]
5.3 [10]
5.3 [10]
13.3 [6]
13.3 [6]
13.3 [6]
13.3 [6]
8.4 [40]
8.4 [40]
13.3 [6]
13.3 [6]
13.3 [6]
13.3 [6]
13.3 [6]
13.3 [6]
D
E
E
Ground
C Outdoor unit
Recommended setting
MAX. CKT.
Breaker for current leakage
BKR (A)
Capacity
30
30
30 A 30 mA or 100 mA 0.1sec. or less
40
40
40 A 30 mA or 100 mA 0.1sec. or less
50
50
50 A 100 mA 0.1sec. or less
60
60
60 A 100 mA 0.1sec. or less
40
40
40 A 30 mA or 100 mA 0.1sec. or less
30
30
30 A 30 mA or 100 mA 0.1sec. or less
50
50
50 A 100 mA 0.1sec. or less
30
30
30 A 30 mA or 100 mA 0.1sec. or less
50
50
50 A 100 mA 0.1sec. or less
40
40
40 A 30 mA or 100 mA 0.1sec. or less
50
50
50 A 100 mA 0.1sec. or less
50
50
50 A 100 mA 0.1sec. or less
50
50
50 A 100 mA 0.1sec. or less
30
30
30A 30mA or 100 mA 0.1sec. or less
30
30
30A 30mA or 100 mA 0.1sec. or less
50
50
50 A 100 mA 0.1sec. or less
40
40
40A 30mA or 100 mA 0.1sec. or less
30
30
30A 30mA or 100 mA 0.1sec. or less
50
50
50 A 100 mA 0.1sec. or less
50
50
50 A 100 mA 0.1sec. or less
30
30
30 A 30 mA or 100 mA 0.1sec. or less
50
50
50 A 100 mA 0.1sec. or less
50
50
50 A 100 mA 0.1sec. or less
40
40
40 A 30 mA or 100 mA 0.1sec. or less
50
50
50 A 100 mA 0.1sec. or less
50
50
50 A 100 mA 0.1sec. or less
50
50
50 A 100 mA 0.1sec. or less
MCA
MOCP
(A)
(A)
25
42
34
57
45
73
53
88
34
57
25
42
45
73
25
42
45
73
34
57
45
73
45
73
45
73
25
42
25
42
45
73
34
57
25
42
45
73
45
73
25
42
45
73
45
73
34
57
45
73
45
73
45
73
23