Modbus / fbp interface
Table of Contents

Advertisement

# Name/Description
184 Prot I threshold
185 Prot I start up threshold
186 Prot I start up time
187 Prot G configuration
0: Prot enable/disable
1: Trip enable/disable
2: Start Up Th
3: Zone sel
4-15: not used
188 Prot G curve type
189 Prot G threshold T=k/I
2
190 Prot G time T=k/I
2
191 Prot G threshold T=k
192 Prot G time T=k
193 Prot G start up threshold
194 Prot G start up time
195 Prot G zone selectivity time
196 Prot Ext G configuration
0: Prot enable/disable
1: Trip enable/disable
2: Start Up Th
3: Zone sel
4-15: not used
197 Prot Ext G curve type
198 Prot Ext G threshold T=k/I
2
2
199 Prot Ext G time T=k/I
200 Prot Ext G threshold T=k
201 Prot Ext G time T=k
202 Prot Ext G start up threshold
203 Prot Ext G start up time
204 Prot Ext G zone selectivity time
205 Prot U configuration
0: Prot enable/disable
1: Trip enable/disable
2-15: not used
206 Prot U threshold
207 Prot U time
208 Prot UV configuration
0: Prot enable/disable
1: Trip enable/disable
2-15: not used
209 Prot UV threshold
210 Prot UV time
211 Prot OV configuration
0: Prot enable/disable
1: Trip enable/disable
2-15: not used
212 Prot OV threshold
213 Prot OV time
214 Prot RV configuration
0: Prot enable/disable
1: Trip enable/disable
2-15: not used
215 Prot RV threshold
216 Prot RV time
217 Prot RP configuration
0: Prot enable/disable
1: Trip enable/disable
2-15: not used
218 Prot RP threshold
219 Prot RP time
220 Prot UF configuration
0: Prot enable/disable
1: Trip enable/disable
2-15: not used
221 Prot UF threshold
222 Prot UF time
223 Prot OF configuration
0: Prot enable/disable
1: Trip enable/disable
2-15: not used
224 Prot OF threshold
225 Prot OF time
226 Prot OT configuration
0: not used
1: Trip enable/disable
2-15: not used
227 Load control configuration
0: Iw Th enable/disable
1: LC1 Th enable/disable
2: LC2 Th enable/disable
3-15: not used
228 Warning current Iw
229 LC1 threshold
230 LC2 threshold
231 Prot Rc configuration
0: Prot enable/disable
1: Trip enable/disable
2-15: not used
232 Prot Rc threshold
233 Prot Rc time
ABB SACE
Range
Units Multipler Coding
{1,5 ... 15}, step 0.1
In
{1,5 ... 15}, step 0.1
In
{0.10 ... 1.50}, step 0.01
s
Enable | Disable
Enable | Disable
OFF | ON
OFF | ON
T=k | I
2
t = k
{0.20 ... 1.00}, step 0.02
In
{0.01 ... 1.00}, step 0.05
s
{0.20 ... 1.00}, step 0.02
In
{0.01 ... 1.00}, step 0.05
s
{0.20 ... 1.00}, step 0.02
In
{0.01 ... 1.00}, step 0.05
s
{0.04 ... 0.20}, step 0.01
s
Enable | Disable
Enable | Disable
OFF | ON
OFF | ON
T=k | I
2
t = k
{0.20 ... 1.00}, step 0.02
In
{0.01 ... 1.00}, step 0.05
s
{0.20 ... 1.00}, step 0.02
In
{0.01 ... 1.00}, step 0.05
s
{0.20 ... 1.00}, step 0.02
In
{0.01 ... 1.00}, step 0.05
s
{0.04 ... 0.20}, step 0.01
s
Enable | Disable
Enable | Disable
{5 ... 90}, step 5
%
{0.5 ... 60}, step 0.5
s
Enable | Disable
Enable | Disable
{0.50 ... 0.95}, step 0.01
Un
{0.1 ... 5.0}, step 0.1
s
Enable | Disable
Enable | Disable
{1.05 ... 1.20}, step 0.01
Un
{0.1 ... 5.0}, step 0.1
s
Enable | Disable
Enable | Disable
{0.10 ... 0.40}, step 0.05
Un
{0.5 ... 30.0}, step 0.5
s
Enable | Disable
Enable | Disable
{-0.10 ... -0.30}, step -0.02
Pnt
{0.5 ... 25.0}, step 0.1
s
Enable | Disable
Enable | Disable
{0,90 ... 0.99}, step 0.01
Fn
{0.5 ... 3.0}, step 0.1
s
Enable | Disable
Enable | Disable
{1.01 ... 1.10}, step 0.01
Fn
{0.5 ... 3.0}, step 0.1
s
Enable | Disable
Enable | Disable
Enable | Disable
Enable | Disable
{0.30 ... 10.00}, step 0.05
In
{50 ... 100}, step 1
%I1
{50 ... 100}, step 1
%I1
Enable | Disable
Enable | Disable
0.3 | 0.5 | 0.7 | 1.0 | 2.0 | 3.0
Idn
0.06 | 0.10 | 0.20 | 0.30 | 0.40 |
s
0.50 | 0.80 | 1.00 | 3.00 | 4.80
EP010
Lenght
Range
[bytes]
default
100
2
1.5
100
2
1.5
100
2
0.1
2
0 | 1
0 | 1
0 | 1
0 | 1
0 | 1
2
100
2
100
2
100
2
100
2
100
2
100
2
100
2
2
0 | 1
0 | 1
0 | 1
0 | 1
0 | 1
2
100
2
100
2
100
2
100
2
100
2
100
2
100
2
2
0 | 1
0 | 1
2
100
2
2
0 | 1
0 | 1
100
2
100
2
2
0 | 1
0 | 1
100
2
100
2
2
0 | 1
0 | 1
100
2
100
2
2
0 | 1
0 | 1
100
2
100
2
2
0 | 1
0 | 1
100
2
100
2
2
0 | 1
0 | 1
100
2
100
2
2
0 | 1
2
0 | 1
0 | 1
0 | 1
100
2
2
2
2
0 | 1
0 | 1
0 | 1 | 2 | 3 | 4 | 5
2
0 | 1 | 2 | 3 | 4 | 5
2
6 | 7 | 8 | 9
1SDH000510R0001
Notes
Read only PR123 only
T=k
0.2
0.01
0.2
0.01
0.2
0.01
0.04
T=k
0.2
0.01
0.2
0.01
0.2
0.01
0.04
5
0.5
0.50
0.1
1.05
0.1
0.1
0.5
-0.10
0.5
0.9
0.5
1.01
0.5
0.30
50
50
0.3
0.06