4
Mounting/Installation
Configure speaker lines
40 | 122
The jumper settings are changed with the jumper key.
Insert the jumper key to a jumper, pull the jumper out and place it on the new
position.

Fig. 14: PC100x-A3 jumper key

The 16 speaker line zones can be configured to the 4 amplifiers.
The speaker line configuration matrix has 16 columns representing the 16 speaker
line zones and 4 rows representing the 4 amplifiers.
Every second column is a bit offset to ensure jumpers can't be set offset to the
adjacent zone.

Fig. 15: PC100x-A3 speaker line configuration matrix

Fig. 16: Example of PC100x-A3 speaker line configuration matrix

The example shows that:
Amplifier 1 is configured to power the speaker line zones 1-6
Amplifier 2 is configured to power the speaker line zones 7-10
Amplifier 3 is configured to power the speaker line zones 11-14
Amplifier 4 is configured to power the speaker line zones 15 and 16
A6V11899867_en--_a