Setting Elements - Siemens RVP201 Installation Instructions Manual

Hide thumbs Also See for RVP201:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 3
- If it flashes, the detector wiring may be faulty
- If it is lit, the controller is overridden by a remote operation
facility (room unit or changeover switch). Set room unit to
operating mode
or open the external switch)
4. Set operating mode selector to
5. Set heating curve potentiometer
to +8 °C:
- Flow temperature must rise: burner on, valve open, heat-
ing circuit pump on (electro-thermal actuators respond with
a certain delay!)
- If not: check wiring of the detectors (flow/boiler, outside de-
tector), actuator/burner and heating circuit pump
6. Set operating mode selector to .
7. Set heating curve to 0.25 and setting knob
- Burner must switch off (observe minimum running time of
4 minutes), valve must travel toward "colder", and heating
circuit pump must remain activated
- If not: check wiring of the detectors (flow/boiler, outside de-
tector), actuator/burner and heating circuit pump
Commissioning the remote operation facility
1. Set the controller's operating mode selector to one of the two
Auto
positions
2. If a room unit is present: select operating mode
room unit

Setting elements

Refer to figure
on page 24
3
1
Opening for time switch
2
LED for "Override"
3
Operating mode selector
4
Setting knob for heating curve
5
Setting knob for setback
Coding switches
Function
Type of regulating unit
Type of control
Frost protection
D.h.w. priority (only RVP211)
RVP211 with boiler temperature control:
Regulating unit for d.h.w. heating Changeover valve
Setting potentiometers
Settings must be determined during the planning phase.
If missing, the following guide values can be used.
Potentiometer
Function
Switching differential
with two-position
control
Authority of room
temperature on flow
temperature control
Heating limit for ECO
automatic energy
saver
Max. limitation of flow
or boiler temperature
Settings on the controller
1. Set heating curve as specified in the planning documen-
tation or in compliance with local practices.
2. Reset setting knob
to 0 (factory-setting, corresponds
to 20 °C room temperature).
3. Leave setting knob
to –6 °C (factory-setting).
4. Set operating mode selector to one of the two
tions.
5. Set time switch as indicated in the operating instructions.
Building Technologies
.
to 4 and setting knob
to –8 °C:
on the
6
Setting knob for d.h.w. temperature (only RVP211)
7
Setting knob for normal room temperature
8
Coding switches
9
Setting potentiometer for authority of room temperature
and quick setback active / inactive
Switch position on the left
Control of a motorized valve
Three-position (modulating)
Yes, frost protection
With priority (absolute). Underfloor
heating systems and boiler opera-
tions: always set to abs.!
Setting range
1...20 K
0...100 % authority
Off = quick setback is
inactive
–10...+8 K (referred to
the room temperature
set value)
10...100 °C
Auto
posi-
74 319 0614 0 c
- Check the "Override" LED on the controller: must be lit
- If not: check wiring of the room unit
3. If a changeover switch is present: close it (gives operating
mode
on the controller).
- Check the "Override" LED on the controller: must be lit.
- If not: check wiring of the changeover switch
Commissioning of D.h.w. heating
(only RVP211)
1. The D.h.w. temperature must be around 30 °C (check by
touching or use a measuring instrument).
2. Set the controller's operating mode selector to
3. Set setting knob
to 60 °C.
- D.h.w. temperature must rise: charging pump on or
changeover valve open
- If not: check wiring of the d.h.w. temperature detector and
the heating circuit pump, or the changeover valve
4. Set setting knob
to 10 °C (observe overrun time)
- Charging pump or changeover valve must switch off
- If not: check wiring of d.h.w. temperature detector
5. Reset setting knob
to 55 °C (factory-setting).
10 Setting potentiometer for max. limitation of flow or boiler
temperature
11 Setting potentiometer for ECO heating limit
12 Setting potentiometer for switching differential
Symbol
Symbol
Guide value
Notes
Burner control: 6 K
50 % (quick setback
Plants with no room unit: setting is inactive
is active)
Plants with no outside detector:
Setting 0...100 % = quick setback is active
Setting Off = quick setback is inactive
–3 K (gives a heat-
Off = function disabled
ing limit of 17 °C at a
room temperature
set value of 20 °C)
Guide value for un-
Off = function disabled
derfloor and ceiling
heating systems:
55 °C max.
Seal the transparent cover, if required.
Heating curve diagram: Refer to figure
T
Outside temperature [°C]
A
T
Flow temperature [°C]
V
20.05.2008
.
Switch position on the right
Control of a atmospheric or
forced draught burner
Two-position (on/off)
No, no frost protection
No priority (parallel)
Charging pump
on page 24
4
4/26

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rvp211

Table of Contents