Installation Instructions
Air-Fi® Wireless
Communications Interface (WCI)
Model Number:
X13790901030, X13790902030, X13790903030,
X13790904030, X13790941030
X39641361001
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation,
starting up, and servicing of heating, ventilating, and air-conditioning equipment can
be hazardous and requires specific knowledge and training. Improperly installed,
adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
Indicates a potentially hazardous situation which,
WARNING
if not avoided, could result in death or serious
injury.
Indicates a potentially hazardous situation which,
CAUTION
if not avoided, could result in minor or moderate
injury. It could also be used to alert against unsafe
Indicates a situation that could result in
NOTICE
equipment or property-damage only accidents.
June 2020
BAS-SVN038C-EN
© 2020 Trane
4
3
Power OFF
Connect WCI Wires to Controller
Device
Hazardous voltage!
Disconnect all electric power, including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure that power cannot be
inadvertently energized. Failure to disconnect power before servicing could
result in death or serious injury.
UC 210/400/600
WCI
+ 24
VDC
LINK
IMC
UC
1
Set Addresses
For detailed information and procedures, refer to the
following documents:
®
• Air-Fi
Wireless Installation, Operation, and
Maintenance (BAS-SVX40*)
®
• Air-Fi
Wireless Network Design Best Practices
Guide (BAS-SVX55*)
SC - 1
1
1
GRP NET
WCI
1
1
1
1
GRP
NET
GRP NET
WCI
WCI
Device
Device
BCI-I (IntelliPak/CSC)
Jumper
Note: Field-supplied.
24
VAC
BI 1
BI 2
BI 3
BCI-I
Tracer SC/SC+
Use a PM014 with Tracer SC with 1 or more
wireless networks, or Tracer SC+ when needed
to stay within IMC power budget.
IM C
SC - 2
2
1
1
2
GRP
NET
GRP NET
GRP NET
WCI
WCI
2
1
2
1
1
2
1
2
GRP NET
GRP NET
GRP NET
GRP NET
WCI
WCI
WCI
WCI
Device
Device
Device
Device
BCI-R (ReliaTel™: Voyager™, Precedent™, and Odyssey™)
WCI
IM C
+ 24
VDC
LINK
IMC
Connect both 2-connector screw
WCI wiring
terminal blocks to either of the
IMC terminals on the PM014.
Tracer SC+ when IMC power budget allows
PM014
IMC–
IMC+
Ground
24 Vdc
2
Connecting the Wiring Harness to the WCI
2
2
GRP NET
WCI
2
2
2
2
GRP NET
GRP NET
WCI
WCI
Device
Device
WCI
MSTP
WCI as Repeater
WCI Wiring
Tracer SC+
+24 VDC/VAC
Note: It is normal for the
Repeater DIAG LED to flash.
Red = +24VDC/VAC
Black =
Blue = LINK+
Gray = LINK–
5
Power ON Device
Note: If all devices
cannot be powered on at
the same time, the best
practice is to power them
on in the following order:
1. All WCIs
2. All unit controllers:
UC210, UC400,
UC600, BCI-I, BCI-R
3. All Tracer SCs
4. All WCSs