enced subject, which is represented only by the standard
in its entirety.
In Canada, refer to the CSA B149 installation codes.
CAUTION
Do not install the furnace in a corrosive or contaminated
atmosphere. Meet all combustion and ventilation air
requirements, as well as all local codes.
unsafely. Enough air must be provided to meet the needs
of all fuel-burning appliances and appliances such as ex-
es, exhaust fans, or clothes dryers are used at the same
time as the furnace, much more air is required to ensure
cient air causes incomplete combustion which can result
in carbon monoxide.
In addition to providing combustion air, fresh outdoor air
dilutes contaminants in the indoor air. These contaminants
may include bleaches, adhesives, detergents, solvents
and other contaminants which can corrode furnace com-
ponents.
The requirements for providing air for combustion and
ventilation depend largely on whether the furnace is in-
large equipment room with a volume greater than 50 cubic
feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com-
bined input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be
for combustion if the structure does not provide enough air
construction with weather stripping and caulking around
the windows and doors, follow the procedures in the Air
from Outside section.
cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of
the combined input rating of all appliances installed in that
equipment rooms. When the furnace is installed so that
supply ducts carry air circulated by the furnace to areas
outside the space containing the furnace, the return air
must be handled by ducts which are sealed to the furnace
casing and which terminate outside the space containing
the furnace. This is especially important when the furnace
closet or small equipment room.
-
Even a small leak around the base of the unit at the plat-
form or at the return air duct connection can cause a po-
tentially dangerous negative pressure condition. Air for
combustion and ventilation can be brought into the con-
Air from Inside
providing two permanent openings between the two spac-
es. Each opening must have a minimum free area of 1
square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of
space. Each opening must be at least 100 square inches
(64516 mm2). One opening shall be within 12 inches (305
mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See Figure 4.
-
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM INSIDE
-
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE - Each opening shall have a free area of at least one square inch
per 1,000 Btu (645mm
all equipment in the enclosure, but not less than 100 square inches
2).
(64516mm.
Air from Outside
If air from outside is brought in for combustion and ventila-
nent openings. One opening shall be within 12" (305mm)
of the top of the enclosure and one within 12" (305mm) of
the bottom. These openings must communicate directly or
by ducts with the outdoors or spaces (crawl or attic) that
freely communicate with the outdoors or indirectly through
vertical ducts. Each opening shall have a minimum free
area of 1 square inch per 4,000 Btu (645mm2 per 1.17kW)
per hour of total input rating of all equipment in the en-
closure. When communicating with the outdoors through
area of 1 square inch per 2,000 Btu (645mm2 per .59kW)
per total input rating of all equipment in the enclosure (See
Figure 5). It is also permissible to bring in air for combus-
tion from a ventilated attic (Figure 6) or ventilated crawl
space (Figure 7).
Page 6
OPENINGS
(To Adjacent
Unconfined
Space)
2
per .29kW) per hour of the total input rating of
Figure 4
-