Gas furnace upflow / horizontal air discharge
Table of Contents

Advertisement

NOTE − FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
D
B
C1
A
STRAIGHT
APPPLICATION
* WALL
SUPPORT
D
E
B
A
C1
EXTENDED
APPLICATION
ALTERNATE TERMINATIONS (TEE & FORTY−FIVE DEGREE ELBOWS ONLY)
B
D
1
C
2
A
D
1
E
B
12"
C
2
A
1
The exhaust termination tee should be connected to the 2" or 3" PVC flue pipe as shown in the illustration. In
horizontal tee applications there must be be a minimum of 3 ft away from covered patios or any living ares and
cannot be within 3 ft of a window. Do not use an accelerator in applications that include an exhaust termination
tee. The accelerator is not required.
2
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield
(24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield
is recommended. The shield should be constructed using wood, sheet metal or other suitable material.
All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.
3
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust
away from adjacent property. The exhaust must never be directed toward the combustion air inlet.
FIELD FABRICATED WALL TERMINATION
D
B
Intake
C2
Elbow
A
E
A
C2
B
Exhaust
D
C
3
Intake
Elbow
A
D
1
E
B
12"
C
2
A
Figure 42
Page 30
A− Minimum clearance
above grade or average
snow accumulation
B− Maximum horizontal
separation between
intake and exhaust
C1 -Minimum from end of
exhaust to inlet of intake
C2 -Minimum from end of
exhaust to inlet of intake
D− Maximum exhaust
pipe length
E− Maximum wall support
D
distance from top of each
pipe (intake/exhaust)
See maximum allowable venting tables for venting
B
lengths with this arrangement.
* Use wall support every 24" (610 mm). Use two
wall supports if extension is greater than
24" (610 mm) but less than 48" (1219 mm).
NOTE − One wall support must be within 6" (152 mm)
from top of each pipe (intake and exhaust) to prevent
movement in any direction.
2" (51MM)
Vent Pipe
A− Clearance above
grade or average snow
12" (305 mm) Min. 12" (305 mm) Min.
accumulation
B− Horizontal
6" (152 mm) Min.
separation between
24" (610 mm) Max.
intake and exhaust
C− Minimum from
end of exhaust to
9" (227 mm) Min.
inlet of intake
12" (305 mm) Min.
D− Exhaust pipe length
16" (405 mm) Max.
E− Wall support distance
from top of each pipe
6" (152 mm) Max.
(intake/exhaust)
Front View of
Intake and Exhaust
Intake
Exhaust
2" (51mm)
3" (76mm)
Vent Pipe
Vent Pipe
12" (305 mm)
12" (305 mm)
6" (152 mm)
6" (152 mm)
8" (203 mm)
8" (203 mm)
6" (152 mm)
6" (152 mm)
12" (305 mm)
20" (508 mm)
6" (152 mm)
6" (152 mm)
3" (76MM)
Vent Pipe
6" (152 mm) Min.
24" (610 mm) Max.
9" (227 mm) Min.
12" (305 mm) Min.
20" (508 mm) Max.
6" (152 mm) Max.