Programmed / Displayed Data Table - Emerson Dosaodor-D V

Odorant injection system
Table of Contents

Advertisement

Programmed / Displayed Data Table

Data identification code numbers on the system
-Dosaodor-D Rev. 4.17
Language - ENGLISH (International Standards Units)
Programmed Data: from Loc:00 to Loc:06 & Loc:09
a) Loc:00 Dosaodor-D Rev. 4.17
b) Language Messages
c) Date
Day/Month/Year
d) Time
Hour:Minute:Second
a) Loc:00 Dosaodor‑D Rev. 4.17
The active Page Location (Loc) is displayed together with
the Software version installed in the control unit memory.
b) Language Messages
By pressing the ENT key, you can select the Language
for the messages displayed and printed. It is possible
to have other languages, besides ITALIAN/ENGLISH
ENGLISH Pls.,contact your local office for further
information.
c) Date
Enter the current date in European format: Day/Month/
Year
d) Time
Enter the current time in International format:
Hour:Minutes:Seconds
Loc:01 Dosaodor-D Rev. 4.17
a) Odorizing Concentration
b) Gas Volume Input
c) Gas Flowrate (Manual Set)
a) Programmed Odorizing Rate
Odorizing concentration that you intend to inject; it is
expressed in Odorizing mg each m
b) Gas Volume Inlet
"Weight" of the gas volume pulse accessing the system.
Enter the number of gas m
The system is set to receive max. one pulse per
second. Therefore the possible flow computer shall be
programmed adequately to meet this condition.
In the case the control unit is set to acquire an analog
signal of 4-20 mA for Gas Instantaneous Delivery
ENGLISH
04/10/02
15:20:30
mg/m
40 *
3
Pulse=m
3
0010.00 *
m
3
/h 00001000 *
3
of transited Gas.
each received pulse.
3
instead of pulse Volume, set a value in this location that
corresponds the min. value of the equipment.
This value is calculated according to the max. gas
delivery of the station, while taking into consideration
that the equipment can integrate a max. quantity of gas
per second equal to the set value.
c) Gas Delivery (Manual)
Gas Delivery simulated by the equipment in case
MANUAL mode is selected (constant dosing).
*
Loc:02 Dosaodor-D Rev. 4.17
*
a) Specific Volume Inject. n1
*
b) Specific Volume Inject. n2
c) Check Cylinder Od. Volume
a) Specific Volume – Injector No.1
Enter the value written on the label of the pneumatic
panel, that indicates the max. delivery of Injector No. 1
expressed in odorizing grams per opening second.
b) Specific Volume – Injector No.2
Enter the value written on the label of the pneumatic
panel, that indicates the max. delivery of Injector No. 2
expressed in odorizing grams per opening second.
c) Odorizing Volume in the Control Cylinder
Enter the value written on the label of the pneumatic
panel ad multiply it by the specific weight of the used
odorant (THT=1 – Mercaptani=0.8).
Loc:03 Dosaodor-D Rev. 4.17
a) Volume for Switch I1 ↔ I2
b) User Code
c) Printer Interval
a) Volume for Injector Exchange
Used in version Dosaodor-D B2 (dual injector) to set the
grams of injected odorant after which the operating injec-
tor is automatically exchanged. The exchange will take
place only if the Injector 1-2 operation mode is selected.
b) REMI System Code
Enter a numerical value to identify the system. This
number is indicated both on the daily reports and the
header of the data transmitted via serial port.
c) Printer Interval
Enter the value for periodical printing. If you enter
"00:00" ALL printing functions are disabled.
Dosaodor-D
g/s
01.00
g/s
01.00
g
0062.0
g/s
00002000
Number
00000000
Hour:Minute
00:00
*
*
*
*
*
*
27

Advertisement

Table of Contents
loading