Cell210 Cellular-Radio Firmware Update - Campbell CR300 Series Application Note

Cellular module firmware update
Hide thumbs Also See for CR300 Series:

Advertisement

5. CELL210 cellular-radio
firmware update
NOTE:
Only CR3X0-CELL210 data loggers need to update the cellular-radio firmware. This update
ensures that these modems will continue to be compatible with future Verizon network
software updates.
1. Get the latest version of Device Configuration Utility from the Downloads section of
https://www.campbellsci.com/devconfig.
2. Connect the computer to the data logger using a USB cable supplied with CR300 data
logger.
3. Ensure the data logger has 12 VDC power applied.
4. Start Device Configuration Utility. Select the CR300 data logger from the list of devices
presented in the Device Type field.
5. Select the appropriate Communication Port by clicking on the ... button. It should have
CR300 listed in the name. If not, install the appropriate driver by clicking on the Install USB
Driver button.
6. Click Connect.
7. Ensure the data logger has OS 09.00 or greater installed. This is shown in the OS Version
field of the Deployment > Datalogger tab. If it is not, see
8. Select the Settings Editor tab then Cellular. The PPP Authentication Username and PPP
Authentication Password fields, must not be used. If these fields contain information, you
will need to have Campbell Scientific update your module firmware, see
direct access to the data logger nor a copy of LoggerNet
CR300 OS update
If you don't have
(p. 15).
Cellular Module Firmware Update
(p. 2).