Manual Method To Purge Non-Condensable Gas Directly From Absorber - York YHAU-CGN Installation Operation & Maintenance

Direct fired absorption chiller-heater
Table of Contents

Advertisement

FORM 155.32-ICOM2.EN.UL
ISSUE DATE:1/10/2018
MANUAL METHOD TO PURGE NON-CONDENSABLE GAS DIRECTLY
FROM ABSORBER
When the chiller-heater operates at a lower capacity than usual for a long period of time or
when it restarts after a power failure, the absorber may contain non-condensable gases. If
the machine starts under these conditions, the unit performance and efficiency decrease. If
this happens, purge non-condensable gas directly from the absorber manually as outlined
in the following procedure.
1. Set the valves according to Pattern B, see Figure 62 on page 129 and Table 36 on
page 133.
2. Press the Purge Mode Manual button on the Setting screen.
3. Press the Manual Purge ON button. The vacuum pump starts. The solenoid valves
SV1 and SV2 open.
4. After step 3 begins, confirm that vacuum gauge stands at 0 ~1 kPa.abs.
5. Reading the vacuum gauge, open valve V13.
6. Then, open valve V16 gradually. Confirm that the pressure on the vacuum gauge in-
creases slightly.
NOTE: If the pressure decreases when valve V16 opens, the vacuum pump capacity is
too small. Close valve V16 at once and check the purge line.
7. If no problems are found, open valve V16 the rest of the way.
NOTE: Make sure the valve is completely open.
8. Continue to purge for 2 to 3 hours.
9. Close valves V13 and V16.
10. Press the Manual Purge OFF button. The vacuum pump stops.
For information on how to set up an automatic purge, see Automatic Method to Purge Non-
condensable Gas from the Purge Tank on page 128.
JOHNSON CONTROLS
SECTION 7 – MAINTENANCE
127