Honeywell Fire-Lite Alarms SD365R Installation And Maintenance Instructions

Honeywell Fire-Lite Alarms SD365R Installation And Maintenance Instructions

Intelligent photoelectric smoke sensor with remote test capability in duct applications

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
SD365R and SD365R-IV
Intelligent Photoelectric Smoke Sensor
with Remote Test Capability in Duct Applications
SPECIFICATIONS
Operating Voltage Range:
Operating Current @ 24 VDC:
Maximum Alarm Current:
Maximum Current:
Operating Humidity Range:
Operating Temperature Range:
Air Velocity:
Height:
Diameter:
Weight:
Isolator Load Rating:
*Please refer to your isolator base/module manual for isolator calculation instructions.
UL268A listed for Duct Applications
This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when
installed in compliance with the National Fire Protection Association (NFPA);
see NFPA 72.
GENERAL DESCRIPTION
Models SD365R and SD365R-IV are plug-in type smoke sensors that combines
a photoelectronic sensing chamber with addressable-analog communications.
When used in duct applications with a DNR(W), testing can be done remotely
using approved System Sen sor test accessories, eliminating the need for a test
coil. The sensors transmit an analog representation of smoke density over a
communication line to a control panel. Rotary dial switches are provided for
setting the sensor's address.
FIGURE 1. ROTARY ADDRESS SWITCHES:
7
8
6
9
5
10
4
3
13
2
14
1 0
15
TENS
Two LEDs on the sensor are controlled by the panel to indicate sensor status.
An output is provided for connection to an optional remote LED annunciator
(P/N RA100Z).
Note: Only System Sensor approved accessories may be used with the SD365R
and SD365R-IV.
Fire-Lite panels offer different features sets across different models. As a re-
sult, certain features of the photoelectric sensors may be available on some
control panels, but not on others. SD365R will support only LiteSpeed® pro-
tocol mode. SD365R-IV will support either LiteSpeed or CLIP (Classic Loop
Interface Protocol) mode. The possible features available in the SD365R and
SD365R-IV, if supported by the control panel are:
1. The sensor's LEDs can operate in three ways—on, off, and blinking–and
they can be set to red, green, or amber. This is controlled by the panel.
2. The remote output may be synchronized to the LED operation or con-
trolled independent of the LEDs.
3. Devices are point addressable up to 159 addresses.
Please refer to the operation manual for the UL listed control panel for specific
operation. The SD365R and SD365R-IV require compatible addressable com-
munications to function properly. Connect these sensors to listed-compatible
control panels only.
SPACING
Fire-Lite recommends spacing sensors in compliance with NFPA 72. In low air
flow applications with smooth ceilings, space sensors 30 feet apart (9.1 m).
For specific information regarding sensor spacing, placement, and special ap-
plications, refer to NFPA 72 or the System Smoke Detector Application Guide,
available from Fire-Lite.
Duct Applications: SD365R and SD365R-IV are listed for use in ducts. See
Duct Smoke Detectors Applications Guide HVAG53 for details on pendant
Preliminary
15 to 32 VDC
200 uA (one communication every 5 seconds with green LED blink on communication)
2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)
4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)
10% to 93% Relative Humidity, Non-condensing
32°F to 122°F (0°C to 50°C), -4°F to 158°F (-20°C to 70°C) in duct applications
0 to 4000 ft./min. (0 to 1219.2 m/min.)
2.0˝ (51 mm) installed in B300-6 Base
6.2˝ (156 mm) installed in B300-6 Base; 4.1˝ (104 mm) installed in B501 Base
3.4 oz. (95 g)
0.0063*
7
8
6
9
5
11
4
12
3
2
1 0
ONES
mount applications. NOTE: SD365R and SD365R-IV are also listed for use in-
side DNR(W) duct smoke detectors.
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code,
applicable local codes, and any special requirements of the Authority Having
Jurisdiction. Proper wire gauges should be used. The installation wires should
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the
event of a fire.
Remove power from the communication line before installing sensors.
1. Wire the sensor base (supplied separately) per the wiring diagram, Figure 2.
2. Set the desired address on the sensor address switches, see Figure 1.
3. Install the sensor into the sensor base. Push the sensor into the base while
turning it clockwise to secure it in place.
4. After all sensors have been installed, apply power to the control panel and
activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
C0162-00
Dust covers provide limited protection against airborne dust particles during
shipping. Dust covers must be removed before the sensors can sense smoke.
Remove sensors prior to heavy remodeling or construction.
FIGURE 2. WIRING DIAGRAM:
Remote
Annunciator
+
(+)
+
2
RA
3
(–)
(–)
CLASS A OPTIONAL WIRING
(+)
TAMPER-RESISTANCE
Models SD365R and SD365R-IV include a tamper-resistant capability that pre-
vents their removal from the base without the use of a tool. Refer to the base
manual for details on making use of this capability.
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Test-
ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors
1
CAUTION
CAUTION: Do not loop wire under
terminal 1 or 2. Break wire run to
-
supervise connections.
+
+
+
2
RA
1
1
3
One FireLite Place
Northford, CT 06472
Phone: 203.484.7161
+
+
2
RA
1
3
C0129-10
I56-6524-001
09/23/2019

Advertisement

loading

Summary of Contents for Honeywell Fire-Lite Alarms SD365R

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS SD365R and SD365R-IV Intelligent Photoelectric Smoke Sensor One FireLite Place Northford, CT 06472 with Remote Test Capability in Duct Applications Phone: 203.484.7161 SPECIFICATIONS Operating Voltage Range: 15 to 32 VDC Operating Current @ 24 VDC: 200 uA (one communication every 5 seconds with green LED blink on communication) Maximum Alarm Current: 2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on) Maximum Current:...