Honeywell SS4-AI Installation Manual And Operating Manual
Honeywell SS4-AI Installation Manual And Operating Manual

Honeywell SS4-AI Installation Manual And Operating Manual

Infrared (ir) digital electro-optical fire detector

Advertisement

Quick Links

Installation Guide and Operating Manual
Infrared (IR) Digital
Electro-Optical Fire Detector
Model SS4-AI
(For Special Applications Only – Consult Factory)
Stand-Alone Mode

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell SS4-AI

  • Page 1 Installation Guide and Operating Manual Infrared (IR) Digital Electro-Optical Fire Detector Model SS4-AI (For Special Applications Only – Consult Factory) Stand-Alone Mode...
  • Page 2 In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
  • Page 3 It may also be used to alert against unsafe practices. CAUTION: Symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual. HONEYWELL...
  • Page 4: Table Of Contents

    3.2 Cleaning Windowed Enclosures and Detectors ........ 14 3.3 Model SS4-AI Detector Faults............15 3.3.1 Detector Faults ..............15 3.4 Model SS4-AI Detector Module Replacement ........15 3.5 Detector Repair................16 DETECTOR PINOUT DATA ............17 TABLE 1: Stand-Alone Model SS4-AI Detector Connectors Pinouts................
  • Page 5: Familiarization

    Detector increases about 15 milliamps in the Stand-Alone mode compared to with connected to theFS2000 System. The Fault relay is not available for use when the Model SS4-AI Detector is wired to the FS2000 System. FS2000 System Operation For FS2000 System operation, the Model SS4-AI Fire and Fault signals are sent digitally to the FS2000 System Controller using the four wire FS2000 FireBus.
  • Page 6: Overview

    Faults are indicated by both LED’s rapidly blinking. (about 2 Hz.) If a Model SS4-AI Detector alarms to a fire, it energizes its Fire relay and turns on its two LED's in the following sequence. One LED is turned on...
  • Page 7 6 minute period may be required in applications where the lens is obscured with great frequency. Fire Detection Range Setting - 15, 30, or 45 feet. The SS4-AI Detector has been calibrated to alarm on an industry standard 1 sq. ft.
  • Page 8: Testing

    The detector uses passive testing for virtually all internal electronic systems. The Model SS4-AI Detectors and the system they are connected to should be periodically manually tested to insure proper function of the entire Fire Protection System. To test the Model SS4-AI Detectors manually (where open fires are might be a safety hazard) for both optical path and window cleanliness, use a Honeywell Analytics Model FT-2145 Test Lamp.
  • Page 9: Installation

    OPERATOR MANUAL // SECTION 2: INSTALLATION SECTION 2: INSTALLATION Installation Procedure This section describes the installation of the Model SS4-AI Detector for the Stand-Alone mode. It is recommended that junction boxes be used to wire the Model SS4-AI Detectors. Determine a mounting location for the detector which is within the detectors range (see Detection Range and Field-of-View) and has a clear view of the fire threat area.
  • Page 10: Wiring Recommendations

    2.1.4 Power Supply Considerations The Model SS4-AI Detector uses 24 volts DC at a maximum current of 75 milliamps. Make sure that the Panel's power supply can handle the current load of the total number of Model SS4-AI Detectors connected to it.
  • Page 11: Enclosure Installation

    Mount the swivel-mount to the wall. Do not install upside down. c. Install the mounting bracket onto the Model SS4-AI Detector enclosure using ¼-20 screws and nuts provided. Be sure the bracket is mounted with the correct orientation. The outside contours of the mounting ears on the Detector enclosure and the ends of the bracket will match.
  • Page 12: Configuring And Wiring Detectors

    Figure 4: Model SS4-AI Detector Enclosure Rear View Configuring and Wiring Detectors To configure and wire a Model SS4-AI Detector, its module has to be removed from the enclosure. After the configuration settings and wiring connections are made, re-install the module in the enclosure.
  • Page 13 J2 connector and firmly tighten down the two slotted screws with a small screwdriver. DO NOT CONNECT ANY WIRES TO Pin 2 or Pin 3. Do NOT over tighten or the screws may strip or break. Refer to Figure 4, Model SS4-AI Detector Wiring. Pin 1 Pin 2...
  • Page 14 Pins 1 and 2 (for Normally Open relays) and firmly tighten down the slotted screws with a small screwdriver. Refer to Figure 4, Model SS4-AI Detector Wiring, for more details on relay connections. 5. REPLACE THE DETECTOR MODULE INTO THE ENCLOSURE.
  • Page 15: Maintenance And Troubleshooting

    TROUBLESHOOTING SECTION 3: MAINTENANCE AND TROUBLESHOOTING Personnel The following will aid in troubleshooting the Model SS4-AI Detector. Tests must be performed by qualified authorized personnel observing standard safety practices. Although the Model SS4-AI Detector operates on safe 24 volts DC, the FM/UL Approved Fire Alarm Panel's power supply may...
  • Page 16: Model Ss4-Ai Detector Faults

    Model SS4-AI Detector Faults 3.3.1 Detector Faults The Model SS4-AI Detector will issue a Fault (or Trouble) condition by de- energizing its Fault Relay (J5 connector). The following are Model SS4-AI Detector Faults: a. Temperature Fault. The Detector will Fault if the internal temperature during operation is above 85°C or falls below -40°C.
  • Page 17: Detector Repair

    Return the defective module to the factory for repair service. There are NO user serviceable parts in a Detector Module. If the Model SS4-AI Module must be shipped back to the factory for repair, it MUST be packed in static protected material. If this material is not available, carefully wrap the Module in aluminum foil.
  • Page 18: Detector Pinout Data

    OPERATOR MANUAL // SECTION 3: MAINTENANCE AND TROUBLESHOOTING DETECTOR PINOUT DATA TABLE 1: Stand-Alone Model SS4-AI Detector Connectors - Pinouts DETECTOR INPUT POWER DC Return or Ground (-) NOT USED (Do not connect to this Pin.) NOT USED (Do not connect to this Pin.)
  • Page 19 The detector is set to detect an industry standard 1 sq. ft. fire at 30 feet on axis. open closed The detector is set to detect an industry standard 1 sq. ft. fire at 45 feet on axis. HONEYWELL...
  • Page 20: Index

    Swivel Mount ......10 Flame Detector See Detector 5 Test Source ......5 Grounding ....... 8 ..........7 Theory of Operation ....5 Troubleshooting ....14 Infrared (IR) Band ....5 Installation ......8 Conduit........8 Visible Band ......5 HONEYWELL...
  • Page 21 Honeywell Analytics warrants its Products against defects in material and workmanship under normal use and service for a period of two (2) years from the date of shipment as described herein. Honeywell Analytics, at its option, will repair or replace, at no charge, such products found to be defective during the warranty period provided that they are returned in accordance with the terms of this warranty.
  • Page 22 Honeywell Analytics Asia Pacific Co., Ltd. #701 Kolon Science Valley (1) 43 Digital-Ro 34-Gil, Guro-Gu Seoul, 152-729 Korea Email: analytics.ap@honeywell.com Internet These Honeywell websites may be of interest to Industry Solution customers. Honeywell Organization Corporate www.honeywell.com Honeywell Analytics www.honeywellanalytics.com Telephone Contact us by telephone at these numbers.
  • Page 23 1998M0915 Rev. A 072014 © 2014 Honeywell International Inc.

Table of Contents