O static load has been reached. speed can be easily adjusted from 1500 to 2300rpm, (SDRA The temperature rise is based on using Chromalox 20” diam- heaters are shipped from the factory with the fan speed set at eter FX-20 flexible duct. The performance curves were deter- 1800 rpm).
Page 4
SDRA heaters can be easily field if modified to vary the fan Temperature Rise vs Duct Length speed. There may be some circumstances where the use of 30 kW short lengths of duct may not create sufficient pressure drop 1500 to achieve the desired temperature rise.
Page 5
Accessories Adjustable Damper and Duct Adapter Front of Heater Rear of Heater Duct Adapter Adjustable 1/4-20 Wing nut Provided with Damper AD-16 Fan Speed Adjustments Changing the Pitch Diameter of the Sheaves: 6. Loosen the (2) motor tension lock nuts and the fan belt tension adjusting bolts.
7. Loosen the set screw on the fan pulley or motor pulley. Table B Fig. 3 shows the construction of the fan pulley, the motor No. of turns from No. of turns from full pulley is the same construction. full closed closed Motor Motor...
Page 7
Motor Run these Wires Through 1/2" Amber Pilot Light Conduit Green Pilot Light Cutout Inlet Thermostat Outlet Thermostat Toggle Switch Motor Relay Transformer Front 30 Amp Fusing Contactor Heater 45 Amp Fusing Contactor Run these Wires through 1/4" Conduit Heater Terminal Box Control Enclosure One end attached to screw in terminal box...
Parts Location Front of Heater View Showing Element Placement and Routing of Thermostat Capillary and Mounting of Bulb Element Assembly 30kW Element Assembly 48kW (20-1/2) Front of Heater Twist Wire View Showing Element Placement (30-1/4) and Routing of Thermostat Capillary and Mounting of Bulb Front View Shown with Grille Removed Element Assembly 60kW...