Industrial Shipment Settings And User Range Settings Offset/Gain Value (Buffer Memory Address 202 To 233: Un\G202 To Un\G233) - Mitsubishi Electric Melsec Q Series User Manual

Analog-digital converter module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.4.15 Industrial shipment settings and User range settings offset/gain value
(buffer memory address 202 to 233: Un\G202 to Un\G233)
3 - 33
(1)
Areas used to restore the user range settings offset/gain values when online
module change is made.
Refer to chapter 7 for details of online module change.
(2)
When the offset/gain values of the user range setting are restored, the used data
are stored.
The data are stored (saved) when:
• Initial setting write is performed by the utility;
• The operating condition is set (Operating condition setting request (Y9) turns
from off to on
• The offset/gain values are written in the offset/gain setting mode (User range
writing request (YA) turns from off to on).
1: The data are not saved when values have been written to Mode switching
setting (buffer memory address 158, 159: Un\G158, Un\G159).
(3)
When restoring the offset/gain values of the user range setting, set the data
saved here similarly into the corresponding area of the module where the data
will be restored.
(4)
Buffer memory saving recording procedure for online module change
1) Set Pass data classification setting
2) Turn Operating condition setting request (Y9) from off to on.
3) Compare the offset/gain values of Industrial shipment settings and User range
settings (buffer memory addresses 202 to 233: Un\G202 to Un\G233) with the
range reference values. Refer to Section 7.4 for the range reference values.
4) If the values are proper, record the offset/gain values of Pass data
classification setting
1: The Q68ADV and Q68ADI do not require the setting and recording of Pass
data classification setting.
POINT
Refer to Section 4.6 for the offset/gain value setting method.
1
); or
1
1
, Industrial shipment settings and User range settings.
(buffer memory address 200: Un\G200).
MELSEC-Q
3 - 33