Troubleshooting - Emerson FISHER EZH Series Instruction Manual

Pressure reducing regulators
Hide thumbs Also See for FISHER EZH Series:
Table of Contents

Advertisement

Types EZH and EZHSO
Type SA/2 Pilot Supply Filter Regulator
Maintenance (Figure 26)
1. Disconnect pilot supply filter regulator and remove
it from the line.
2. Remove bolts, washers and nuts (keys 2, 9 and 10)
from the body (key 7), then separate upper and lower
covers (keys 19 and 11) from the body (key 7). When
separating the covers from the body, be aware of loose
components: (keys 1, 3, 4, 8, 12, 18, 20 and 21).
3. Remove and inspect O-ring (key 13) for damage or
wear and replace if necessary. Lightly lubricate the
O-ring before placing it back in the filter cover (key 11).
4. Clean nets (key 8). Replace filter pad (key 12).
5. Inspect diaphragm (key 18) for damage or wear and
replace if necessary. Check the seating surface of the
screw unit (key 17) for erosion, scratches, spurs or
other damage and replace if necessary.
6. Unscrew and remove the regulator seat (key 5). Inspect
the O-ring (key 6) for damage or wear and replace if
necessary. Lightly lubricate the O-ring and place it on
the regulator seat.
7. Pull pad holder unit (key 15) out of the body (key 7).
Inspect the seat for damage, replace if necessary.
8. Set the filter net (key 8) on the spring (key 14) and
insert the regulator seat (key 5). Tighten the regulator
seat until it stops.
9. Lightly lubricate the outer and inner rims of the
diaphragm (key 18). Place the diaphragm assembly
on top of the regulator seat (key 5). The screw unit
(key 17) will slide into the regulator seat (key 5). Take
care to avoid damage to parts when reassembling.
10. Set the spring (key 1, version Type EZH spring
diameter 3, on top of the nut (key 21).
11. Align the regulator cover (key 19) over the body
(key 7), with the sense port (V) opposite the pilot
supply port (R).
12. Place the filter pad (key 12) and nets (key 8), one on
each side of the filter pad, on the filter cover (key 11).
13. Pick up the body (key 7) and place it on the filter cover
(key 11), with the inlet port (M) aligned vertically with
the sense port (V).
14. Insert bolts (key 2). Place washers (key 9) and nuts
(key 10) on the end of the bolts. Tighten the nuts.
26

TROUBLESHOOTING

Servicing Check
Operations concerning the integral slam-shut
version are in italic.
Recommended frequency
• 2 times per year
Verification
• Set point verification
• Regulator valve plug tightness
• Tripping and setpoint value
• Slam-shut valve tightness
Starting positions
• Inlet valve
• Outlet valve
• Slam-shut valve plug
• Regulator
Inlet and outlet side of the regulator are under pressure.
Tight shut-off verification (and tripping verification
for versions with integral slam shut)
• Inlet valve
• Outlet valve
• Regulator
Open
à
Open
à
à
Open
In operation
à
Closed
à
Closed
à
Observe the evolution
of the outlet pressure
Control regulator tightness