Breaker Functions - GE Feeder Management Relay 750 Instruction Manual

Table of Contents

Advertisement

5 SETPOINTS
PATH: SETPOINTS
S3 LOGIC INPUTS
BRKR FUNCTIONS
[ENTER] for more
The following logic functions are used to determine whether the circuit breaker is open, closed, or disconnected from the
main power circuit, as monitored by auxiliary contacts on a drawout breaker racking mechanism, or on the associated iso-
lating disconnect switches on a fixed circuit breaker.
If neither the 52a or 52b contacts are installed then the following functions cannot be performed:
Monitoring of breaker position
Breaker Operation Failure
Feedback control of Trip (Output Relay 1) and Close (Output Relay 2) relays
Trip/Close Coil Supervision Without Permissive
Manual close feature blocking
Autoreclose
Transfer
It is strongly recommended that the Breaker Operation Failure alarm be enabled when either 52a or 52b
breaker auxiliary contacts are installed.
CAUTION
Breaker logic functions must be assigned to Logic Inputs 1 to 14 as they must only be contacts.
CAUTION
The
and
52a CONTACT
52b CONTACT
mines how these contacts affect the breaker state:
52/A CONTACT
52/B CONTACT
INSTALLED?
INSTALLED?
Yes
Yes
No
No
When asserted, the logic input assigned by the
primary system. When the breaker is determined to be disconnected, the breaker state is shown to be neither open nor
closed. For further information regarding operation with only one auxiliary breaker contact, see Section 4.1.2: LED Status
Indicators on page 4–2.
GE Multilin
Courtesy of NationalSwitchgear.com
BRKR FUNCTIONS
ð
ENTER
52a CONTACT:
ESCAPE
Disabled
52b CONTACT:
ESCAPE
MESSAGE
Disabled
BRKR CONTACT:
ESCAPE
MESSAGE
Disabled
setpoints are used to monitor the 52/a and 52/b contacts. The following table deter-
INTERPRETATION
Yes
52a closed indicates breaker is closed
52b closed indicates breaker is open
No
52a closed indicates breaker is closed
52a open indicates breaker is open
Yes
52b open indicates breaker is closed
52b closed indicates breaker is open
No
Breaker status unknown
BRKR CONNECTED
750/760 Feeder Management Relay

5.4.3 BREAKER FUNCTIONS

Range: Input 1 to Input 20, Disabled
Range: Input 1 to Input 20, Disabled
Range: Input 1 to Input 20, Disabled
setpoint indicates that the breaker is connected to the
5.4 S3 LOGIC INPUTS
5-21