5 SETPOINTS

5.2S1 RELAY SETUP

PATH: SETPOINTS
S1 RELAY SETUP

PASSCODE

[ENTER] for more
If the passcode security feature is enabled, the setpoint access jumper must be installed on the rear terminals and a pass-
code must also be entered to program setpoints. When the relay is shipped from the factory the passcode is defaulted to
"0". When the passcode is "0", the passcode security feature is always disabled and only the setpoint access jumper is
required for changing setpoints from the front panel.
The
ALLOW ACCESS TO SETPOINTS
points cannot be entered. To regain setpoint access, select "Yes" and follow directions to enter the previously programmed
passcode. If the passcode is correctly entered, entering new setpoints will be allowed. If no keys are pressed for longer
than 30 minutes, setpoint access automatically becomes restricted. Removing the setpoint access jumper immediately
restricts setpoint access. If passcode protection is active but the passcode is not known, contact GE Multilin with the
value.
ENCRYPTED PASSCODE
a) MAIN MENU
PATH: SETPOINTS
S1 RELAY SETUP

COMMUNICATIONS

[ENTER] for more
The 750/760 relay has setpoints to enable communications through its RS232 and RS485/422 ports. Setpoints are also
provided for configuring DNP communications through one of these ports.
GE Multilin
Courtesy of NationalSwitchgear.com
PASSCODE
ð
ENTER
SETPOINT ACCESS:
ESCAPE
Allowed
RESTRICT ACCESS TO
ESCAPE
MESSAGE
SETPOINTS: No
ALLOW ACCESS TO
ESCAPE
MESSAGE
SETPOINTS: No
CHANGE PASSCODE?
ESCAPE
MESSAGE
No
ENCRYPTED PASSCODE:
ESCAPE
MESSAGE
AIKFBAIK
setpoint is only displayed when
COMMUNICATIONS
ð
ENTER
PORT SETUP
ESCAPE
[ENTER] for more
DNP CONFIGURATION
ESCAPE
MESSAGE
[ENTER] for more
750/760 Feeder Management Relay
Range: Allowed, Restricted
Range: Yes, No. Seen only if the passcode is not "0" and
SETPOINT ACCESS
Range: Yes, No. Seen only if
to "Restricted".
Range: Yes, No.
Range: Cannot be edited.
is "Restricted". In this state, new set-
SETPOINT ACCESS
5.2.2 COMMUNICATIONS
See page 5–8.
See page 5–9.
5.2 S1 RELAY SETUP
5.2.1 PASSCODE
is "Allowed".
SETPOINT ACCESS
is set