ALLOW CONTINUOUS FAN DURING UNOCCUPIED
HOURS (20) — The fan can be configured by the user to run
continuously (set to ON) or only during heating or cooling (set
to AUTO). When the fan is set to ON (run continuously), the
Allow Continuous Fan During Unoccupied Hours configura-
tion determines whether the fan will run during unoccupied
periods when heating or cooling is not active.
When the configuration is set to ON and the fan is set to
ON, the fan will run continuously during unoccupied periods,
even when heating or cooling is not active.
When the configuration is set to OF, the fan will run during
unoccupied periods only when heating or cooling is active.
The default is On.
KEYPAD LOCKOUT SELECTION (21) — The
stat has a lockout feature which will not acknowledge configu-
ration buttons until the lockout code is entered. After the
lockout code has been entered, the keypad will remain
unlocked until the user has stopped pressing keys for 2 min-
utes. The Lockout selection can be set to ON or OF (disabled).
Use the Up or Down buttons to toggle between off and on. The
default is OF.
NOTE: If the Lockout is enabled, the lockout code is as fol-
lows, in sequence, within a 10-second time period: Mode
button, Copy Previous Day button, Set Time/Temp button,
and Hold button.
Step 6 — Check Thermostat Operation —
form the following procedure to check thermostat operation:
1. Press the Hold button. This will prevent the set point
from changing until the desired time and temperature
schedule is entered.
2. Press the Fan button to switch the fan annunciator
from AUTO to ON. The fan should run continuously.
Check fan operation. Press the fan button again to
switch back to AUTO.
NOTE: If fan does not run check set up option 20 con-
figuration. Fan may not run during unoccupied times
in schedule.
3. Press the Mode button repeatedly until HEAT is dis-
played in the mode annunciator. Press the Set Time/
Temp button until the heat set point annunciator is
flashing. Press the Up button until the set point reads
10 degrees above room temperature. The heating sys-
tem should begin to operate within 5 minutes.
4. Press the Mode button repeatedly until COOL is dis-
played in the mode annunciator. Press the Set Time/
Temp button until the heat set point annunciator is
flashing. Press the Down button until the set point
reads 10 degrees below room temperature. The cooling
system should begin to operate within 5 minutes.
Step 7 — Select Thermostat Operation Set-
tings —
Thermostat operation should be configured. Set
the Fan and Mode configurations to their desired settings.
DAY OF WEEK
Time / Heat / Cool
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
NOTE: The cooling temperature set point must be at least 3 degrees higher than the heating temperature set point.
thermo-
Per-
Table 3 — Daily Schedule Planner
OC1
Time / Heat / Cool
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
Press the Up and Down buttons to select the desired comfort
temperature.
Step 8 — Set Current Time —
button allows the user to change the time displayed on the ther-
mostat. Press the Set Time/Temp button. The display will show
the blinking TIME annunciator. Press the Up and Down but-
tons until the correct time is shown. Hold down the buttons to
quickly move through the time display. The AM and PM an-
nunciators will automatically change. To ensure the schedules
are properly followed, make sure that AM or PM is correct for
the time chosen. When the correct time is shown, press the End
button to exit the Set Time mode.
Step 9 — Set Current Day —
ton will change the day shown on the thermostat display to the
next day. If a schedule has been entered, the thermostat will fol-
low the schedule of the new selected day.
Step 10 — Programming Thermostat Sched-
ules —
Before programming the thermostat, plan the ther-
mostat daily schedule. The schedule is divided into 7 days
(Monday through Sunday). Each day has 4 time periods (OC1,
UN1, OC2, UN2). Each time period has a start time, heating
set point, and cooling set point. Fill in Table 3 as an aid to pro-
gramming the daily schedules.
PROGRAMMING MODE — To program the daily sched-
ules, perform the following procedure:
1. Enter programming mode by pressing the Program
button. The PROGRAMMING annunciator will
appear on the thermostat display. The current day of
the schedule will be displayed and the current pro-
gramming time period of that day will be displayed.
The TIME annunciator will flash.
NOTE: If a programming button is not pushed for
3 minutes, the thermostat will exit programming mode
and any changes made will be saved.
2. Press the Up and Down buttons to set the start time for
the schedule day and period shown.
3. Press the Set Time/Temp button once the correct time
is shown. The TIME annunciator will stop flashing
and the HEAT annunciator will start flashing.
4. The heating and cooling set points can now be pro-
grammed. The HEAT and COOL annunciators are dis-
played for the heating and cooling set points
respectively. The Set Time/Temp button is used to tog-
gle between the heating and cooling set points and the
time. Use the Up and Down buttons to raise and lower
the temperature set points.
NOTE: There must be at least 3 degrees difference
between the cooling and heating set points. The ther-
mostat will automatically change any set points closer
than 3 degrees.