3
Engineering
Modbus registers
Differential pressure 2
Addr.
Description
4x0065
Reliability.
4x0066
Value
4x0067
Unit
4x0068
Value [Pa]
4x0069
Value [PSI]
4x0070
Zero point calibration
4x0071
Sensor 2 full scale value
4x0072
Average 500 ms
4x0073
Average 1000 ms
4x0074
Average 4000 ms
4x0075
Average 16000 ms
Flow (Diff-pressure Sensor 1)
Addr.
Description
4x0081
Flow low
4x0082
Flow high
4x0083
K-factor
4x0084
Unit
Flow (Diff-pressure Sensor 2)
Addr.
Description
4x0091
Flow low
4x0092
Flow high
4x0093
K-factor
4x0094
Unit
16 | 20
Unit
Scaling
R/W Area
1
R
1
R
1
R/W 0 = Pa = Default
Pa
1
R
PSI
0.0001
R
1
R/W 0 = No action (toggle bit)
Pa
1
R
See config #4x0067
R
See config #4x0067
R
See config #4x0067
R
See config #4x0067
R
Unit
Scaling
R/W Area
0.01
R
0.01
R
1
R/W 0 ≤ VAL ≤ 1500
1
R/W 0 = m³/h (Default)
Unit
Scaling
R/W Area
0.01
R
0.01
R
1
R/W 0 ≤ VAL ≤ 1500
1
R/W 0 = m³/h (Default)
1 = PSI
2 = mmHG
3 = mmH2O
1 = Zero point calibration P1+P2
2 = Zero point calibration P2
3 = Zero point reset to factory setting
P1+P2
4 = Zero point reset to factory setting P2
1 = m³/s
2 = l/s
1 = m³/s
2 = l/s
Data type
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
Data type
uint16_t
uint16_t
uint16_t
uint16_t
Data type
uint16_t
uint16_t
uint16_t
uint16_t
A6V11841988_en--_b