11. Installation Instruction

11.1 Select the Best Location

(For CU-4E27QBR and CU-5E34QBR only)
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
Refrigerant piping size
Outdoor Unit
Liquid - side
Gas - side
* In case of indoor is CS-MRE24***, then ø 12.7
t0.8 gas-pipe size must be used together with
CZ-MA2P (pipe size expander)
Outdoor Unit
Equivalent length
If total piping length of all indoor units exceeds the
equivalent length listed aboved, additionally
charge with 20 g of refrigerant (R410A) for each
additional meter of piping.
Outdoor Unit
Allowable piping length of each indoor unit (min. ~ max.)
Allowable total piping length of all indoor unit
Height difference between indoor and outdoor unit
Height difference between indoor unit
CU-4E27***
CU-5E34***
ø 6.35 t0.8 ø
ø 6.35 t0.8
ø 9.52 t0.8
ø 9.52 t0.8
*(ø 12.7 t0.8)
*(ø 12.7 t0.8)
CU-4E27***
CU-5E34***
45 m
45 m
Allowable piping length
Outdoor unit located on upper side
Outdoor unit located otherwise
Outdoor unit located on upper side
Outdoor unit located otherwise
a
b
c
d
46
CU-4E27***
CU-5E34***
3 m ~ 25 m
3 m ~ 25 m
70 m or less
80 m or less
15 m or less
15 m or less
7.5 m or less
7.5 m or less
7.5 m or less
7.5 m or less
15 m or less
15 m or less