Mode 2 (Type H Units Only)
This mode selection is for hydronic heating systems with
single or multiple boilers in primary/secondary piping
configuration with or without Outdoor Air Reset (S4) with
indirect DHW on the system loop (with or without priority).
The system temperature is controlled by the System
sensor (S3). The Indirect DHW sensor (S5) determines
the indirect call/tank setpoint. The system temperature
is boosted to Target Max when using the Indirect DHW
sensor (S5) during an indirect call for heat. Priority mode
toggles off the System Pump (P2) when an indirect call
for heat is present. The Boiler Pump (P1) runs during any
call for heat. The Indirect DHW Pump (P3) runs during an
indirect call for heat with no "off" delay. The Boiler Pump
(P1) and System Pump (P2) delay "off" as user defined in
the ADJUST menu. The System Pump (P2) runs whenever
the system is enabled for heating and the outdoor air
temperature is lower than the WWSD temperature setting
(if utilized) unless an indirect call for heat is present with
priority. See Figure 14 .
MODBUS
VERSA
ENABLE
0–10 / 4–20mA
PIM
S4
S1
S2
P1
FACTORY INSTALLED SENSOR
FIELD INSTALLED SENSOR
Maximum distance 4 system pipe diameters,
1
not to exceed 12" (305 mm)
Figure 14. MODE 2 - Single Boiler with Indirect in System
Loop
Mode 3 (Type H Units Only)
This mode selection is for hydronic heating systems with
single or multiple boilers in primary/secondary piping
configuration with or without Outdoor Air Reset (S4)
with indirect DHW on the boiler loop (with priority). The
system temperature is controlled by the Supply sensor
(S3) whenever the indirect call for heat is not active. The
DHW Supply sensor (S5) determines the indirect call/tank
setpoint. During an indirect call for heat the boiler firing
rate is determined by the water temperature at the Indirect
AQUASTAT
LOCATED IN
OUTLET PIPE
S5
P3
P2
S3
1
F10710
Supply sensor (S6) and the Target Max setting when using
the Indirect DHW sensor (S5). The Boiler Pump (P1) runs
during all heat calls regardless of priority. The Indirect
DHW Pump (P3) runs during an indirect call for heat with
no "off" delay. The Boiler Pump (P1) and System Pump
(P2) delay "off" as user defined in the ADJUST menu. The
system pump (P2) runs whenever the system is enabled
for heating and the outdoor air temperature is lower than
the WWSD temperature setting (if utilized) unless an
indirect call for heat is present. See Figure 15.
NOTE: A Tank Aquastat can be used in lieu of the
Indirect DHW Sensor (S5). See the VERSA IC ® manual
(241493) for additional details.
NOTE: In cascade configuration, the system pump and
DHW pump (if applicable) outputs from each cascade
member and must be connected in parallel to active
the system pump and DHW pump during "limp-along"
operation respectively. See the VERSA IC ® Manual
(241493) for additional details.
MODBUS
VERSA
ENABLE
PIM
0-10 VDC / 4-20mA
S4
P1
S2
S1
FACTORY INSTALLED SENSOR
FIELD INSTALLED SENSOR
Maximum distance 4 system pipe diameters,
1
not to exceed 12" (305 mm)
Figure 15. MODE 3 - Single Boiler with Indirect on Boiler
Loop

Domestic Hot Water

When designing the water piping system for domestic hot
water applications, water hardness should be considered.
Table G indicates the suggested flow rates for soft, medium
and hard water. Water hardness is expressed in grains per
gallon.
AQUASTAT
LOCATED IN
OUTLET PIPE
S6
P3
1
S3
MODE 3
1
S5
P2
F10516