18.3
Fault history clear
Fault history clearing procedure
• Set Er.CL Fault history clear = "1" to clear the fault history.
Operating procedure
1.
Turning ON the power of the inverter
The operation panel is in the monitor mode.
2.
Selecting the parameter setting mode
Press the MODE key to choose the parameter setting mode. (The parameter number read previously appears.)
3.
Selecting the parameter
Turn the setting dial or press the UP/DOWN key until "ER.CL" (Fault history clear) appears. Press the SET key to
read the present set value. "0" (initial value) appears.
4.
Fault history clear
Turn the setting dial or press the UP/DOWN key to change the value to "1". Press the SET key to start clearing.
"1" and "ER.CL" are displayed alternately after the fault history is cleared.
• Turn the setting dial or press the UP/DOWN key to read another parameter.
• Press the SET key to show the setting again.
• Press the SET key twice to show the next parameter.
502
18. Checking and Clearing of Settings
18.3 Fault history clear