Specifications; Ordering Information - Honeywell W7100 Manual

Discharge water temperature control
Table of Contents

Advertisement

W7100G DISCHARGE WATER TEMPERATURE CONTROL

SPECIFICATIONS

W7100G Model Features:
• 6 stage cooling, controls reciprocating chillers.
• W7101 satellite expansion to 10 cooling stages.
• Adjustable setpoint.
Dimensions: See Fig. 1.
Electrical Ratings:
Input Voltage and Frequency (terminals TR-TR):
At 60 Hz: 20 to 30 Vac.
At 50 Hz: 20 to 26.4 Vac.
Power Consumption:
Device: 12 VA at 24 Vac and 50 to 60 Hz.
On/Off Stages (Cool 1 through 6): See Table 1.
Table 1. Power Consumption On/Off Stages (Cool 1-6).
Contact
Voltage (Vac)
N.O.
24
N.C.
24
N.O.
120/240
N.O.
120/240
Switching: Spdt relays.
Wiring Terminals: 1/4 in. quick-connect.
Sensor Input Signal (See Fig. 2):
Positive temperature coefficient: 4.8 ohms/°F (2.6 ohms/°C).
Resistance: 3484 ohms at 77°F (25°C).
Number of Stages Input:
Resistor value (across terminals 7 and 6) to determine num-
ber of ON/OFF stages. (See Table 2).
Temperature Ratings:
Ambient: -40°F to +150°F (-40°C to +66°C).
Shipping: -30°F to +150°F (-34°C to +66°C).

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-4046—1
Inrush (VA) Running (VA)
240
60
75
30
750
75
240
40
Humidity Rating: 5 to 90 percent RH noncondensing.
Mounting: Four mounting holes in base. Use No. 6 screws
(not provided).
Approvals:
Underwriter's Laboratories Inc. Component Recognized.
Additional System Components:
C7170A1010 Discharge Water Sensor: senses discharge
water temperature, provides input to W7100G sensor
terminals T and T1.
Transformer (required): Provides 24 Vac power for all
components of the W7100G control system.
(Size transformer to match system load.)
Accessories:
T7047C1025 Remote Temperature Sensor: Discharge water
temperature reset from controlled space.
S96381037 Reset Setpoint Potentiometer: Use one or more
T7047C1025 with S963B1037.
C7031G1016 Outdoor Air Sensor: Reset of discharge water
from outdoor air temperature.
C7170A1010 Discharge Water Temperature Sensor: Senses
discharge water temperature for input to W7100G.
W7101A1003 Satellite Sequencer: Adds up to 4 ON/OFF
stages of cooling to W7100 switching capability.
121371A Copper Immersion Well: Required for C7170A
Immersion Sensor.
121371E Stainless Steel Immersion Well Required for
C7170A Immersion Sensor.
107406 Heat Conduction Compound: Required for minimum
thermal lag.
AT72D1683 System Transformer: 40 VA, 120 Vac.
AT87A1106 System Transformer: 50 VA, 120/208/240 Vac.
AT88A1005 System Transformer: 75 VA, 120 Vac.
AT88A1021 System Transformer: 75 VA, 208/240 Vac.
4074EDJ Resistor Kit and Test Plug: Used in controller
checkout.
4074EFV Resistor Kit for W7100G System Configuration:
Used to select number of stages controlled.
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

W7100gW7100g1001/u