Change for life Service Manual Models: GTH(09)CA-K6DNA1A/I GTH(12)CA-K6DNA1A/I GTH(18)CA-K6DNA1A/I GTH(24)CB-K6DNA2A/I Models: (Refrigerant R32) GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI...
Service Manual Part : Technical Information 1. Summary Indoor Unit GTH(09)CA-K6DNA1A/I GTH(12)CA-K6DNA1A/I GTH(18)CA-K6DNA1A/I GTH(24)CB-K6DNA2A/I Remote Controller YT1F(MOTO) Technical Information...
Page 4
Service Manual Parameter Unit Value Model GTH(09)CA-K6DNA1A/I GTH(12)CA-K6DNA1A/I Product Code CN610N0130 CN610N0140 Rated Voltage 220-240 220-240 Power Rated Frequency Supply Phases Cooling Capacity 2600 3500 Heating Capacity 2700 4000 Cooling Power Input Heating Power Input Cooling Current Input 0.17 0.17 Heating Current Input 0.17...
Page 5
Service Manual Parameter Unit Value Model GTH(18)CA-K6DNA1A/I GTH(24)CB-K6DNA2A/I Product Code CN610N0150 CN610N0160 Rated Voltage 220-240 220-240 Power Rated Frequency Supply Phases Cooling Capacity 4500 7100 Heating Capacity 5000 8000 Cooling Power Input Heating Power Input Cooling Current Input 0.17 0.26 Heating Current Input 0.17 0.26...
Page 6
Service Manual Note: Nominal capacities are based on the follow conditions. Mode Indoor Outdoor DB:27 (80.6) DB:35(95) Cooling WB:19 (66.2) WB:24(75.2) DB:20 (68) DB:7(44.6) Heating WB:--(--) WB:6 (42.8) Duct type、 Piping Cassette type\ Length Floor ceiling type The air volume is measured at the relevant standard external static pressure. Noise is tested in the semianechoic room, so it should be slightly higher in the actual operation due to environmental change.
Service Manual 5. Electrical Part 5.1 Wiring Diagram Symbol Symbol Color Symbol Symbol Color Symbol Name White Green Jumper cap Yellow Brown COMP Compressor Blue Grounding wire YEGN Yellow/Green Black Violet Orange 600007060230 Technical Information...
Service Manual 5.2 PCB Printed Diagram Top view Name Ambient temperature sensor Tube temperature sensor Wired controller terminal Terminal of gateway control needle stand Neutral wire terminal Fuse Motor terminal Connection wire terminal for indoor unit and outdoor unit 10 Jumper cap terminal Up&down swing terminal 1 12 Up&down swing terminal 2 Terminal of display needle...
Service Manual 6. Function and Control 6.1 Remote Controller Introduction set fan speed operation mode auto mode send signal health function cool mode I feel dry mode ventilation operation X-fan mode fan mode set temperature heat mode turbo mode set time TIMER ON/TIMER clock sleep mode...
Page 12
Service Manual AUTO COOL DRY HEAT Technical Information...
Page 13
Service Manual no display (horizontal louvers stops at current position) no display Technical Information...
Page 14
Service Manual Sketch map for replacing batteries Technical Information...
Service Manual 6.2 Brief Description of Modes and Functions 1.Basic function of system (1)Cooling mode (2)Drying mode (3) Protection status is same as that under cooling mode. (3)Heating mode (2) Working condition and process for heating mode: (4)Working method for AUTO mode: 1.Working condition and process for AUTO mode: C.
Page 16
Service Manual (7)I feel control mode temperature sent by remote controller. (8)Compulsory defrosting function (1) Start up compulsory defrosting function up after malfunction or protection is resumed. (2) Exit compulsory defrosting mode complete unit will resume normal heating operation. (9)Refrigerant recovery function: (1) Enter refrigerant recycling function (2) Exit refrigerant recycling function (10)Ambient temperature display control mode...
Page 17
Service Manual Instructions to the Error Indicating Lamps on the Panel of the Floor Ceiling Type Unit. Fig.1 States of the Indicating Lamps: ①. Indicating Lamp of “POWER”: The indicating lamp will shine when power on, while it will go out when power off. .
Service Manual Part : Installation and Maintenance 7. Indoor Unit Installation 7.1.1 7.1.2 Installation and Maintenance...
Page 19
Service Manual 7.1.3 Installation and Maintenance...
Page 20
Service Manual 7.1.4 7.1.5 09/12/18K Installation and Maintenance...
Page 21
Service Manual 7.1.6 7.1.6.1 7.1.6.2 R Installation and Maintenance...
Page 22
Service Manual R 7.1.6.3 7.1.6.4 Installation and Maintenance...
Page 23
Service Manual 7.2 Electrical Wiring 7.2.1 Wiring Precautions WARNING! 1.Before obtaining access to terminals, all supply circuits must be disconnected. 2.The rated voltage of the unit is as shown as Table 3 3.Before turning on, verify that the voltage is within the 198-264V range (for single phrase unit) ...
Page 24
Service Manual Fig. 27 Fig. 28 (3). How to fix connection cord and power cord by cord clamp After passing the connection cord fasten it with the cord clamp. (Fig. 28) WARNING! 1.Before starting work, check that power is not being supplied to the indoor unit and outdoor unit. 2.Match the terminal block numbers and connection cord colors with those of the indoor unit side.
Page 25
Service Manual Please read this operating manual carefully before operating the unit. to the material objects for reference. The Refrigerant ● To realize the function of the air conditioner unit, a special refrigerant circulates leads to explosion . It can ●...
Page 26
Service Manual Safety Precautions This mark indicates procedures which, if improperly performed, might lead to WARNING! the death or serious injury of the user. This mark indicates procedures which, if improperly performed, might CAUTION! possibly result in personal harm to the user, or damage to property. WARNING! (1).
Page 27
Service Manual Installation Dimension Diagram Notes: The connection pipe and duct for this unit should be prepared by the user. Installation and Maintenance...
Service Manual 8. Maintenance 8.1 Error Code List Table 1 Fault Display on Indoor Wired Controller Origin of Error Malfunction malfunction Control description code name signal When outdoor unit detects the high pressure switch is cut off for 3s successively, high pressure protection will occur. All the loads (except High pressure High pressure the 4-way valve in heating mode) will be switched off.
Page 29
Service Manual Origin of Error Malfunction malfunction Control description code name signal If the outdoor ambient temperature sensor is detected of open circuit or Malfunction of Outdoor short circuit for 5s successively, outdoor ambient temperature sensor outdoor ambient malfunction will be reported. The unit can automatically resume ambient temperature operation after the malfunction disappears.
Page 30
Service Manual Installation and Maintenance...
Page 31
Service Manual R Installation and Maintenance...
Page 32
Service Manual Installation and Maintenance...
Page 33
Service Manual Installation and Maintenance...
Page 34
Service Manual Installation and Maintenance...
Page 35
Service Manual Installation and Maintenance...
Service Manual 9. Exploded View and Parts List The component picture is only for reference; please refer to the actual product. Installation and Maintenance...
Service Manual Caution: discharge the refrigerant 10. Removal Procedure completely before removal. Installation and Maintenance...
Page 40
Service Manual Installation and Maintenance...
Page 41
Service Manual Disassembly of fan and motor components Remark: Make sure that the power supply is cut off before disassembling and protect all the parts during disassembly, especially the fastening screws for fans. Step Illustration Handling Instruction ●Press the buckle at the joints of front and back scroll cases with hands and pull upward to remove...
Page 42
Add: West Jinji Rd, Qianshan, Zhuhai,Guangdong, China, 519070 Tel: (+86-756) 8522218 Fax: (+86-756) 8669426 E-mail: gree@gree.com.cn www.gree.com HONG KONG GREE ELECTRIC APPLIANCES SALES LIMITED Add: Unit 2612,26/F.,Miramar Tower 132 Nathan Road,TST,Kowloon,HK Tel: (852) 31658898 Fax: (852) 31651029 For product improvement, specifications and appearance in this manual are subject to change without prior notice.