Installation Instruction VARIODYN
2

Standards and Directives

An emergency audio warning system (AWS) or a voice alarm system (VAS) as defined by the DIN VDE 0833-4
and TRVB 158 S standards must consist of components that meet the standards of the DIN EN 54 series. It must
be ensured that these components interact together in line with the function.
However, some installation and configuration practices may contravene EN54 requirements. In this case the
application must meet the local standards and requirements for the application regarding the instructions and
specifications given in this manual.
Devices for use in demanding ambient conditions, such as cold stores, galvanising plants, or corrosive atmospheres,
must be suitable for this particular application or must be adapted using appropriate protective measures.
The functionality of the voice alarm system (VAS) depends on the operating system software used and on the
system configuration. The terminal assignments and connections depicted in these installation instructions refer
exclusively to the specifics of the operating system software version used at the time this product was shipped.
As a result of building-specific programming, the information on the display may differ from the figures and
descriptions provided here.
The system may only be installed in dry, clean, and adequately lit areas with restricted access. The ambient
conditions must correspond to class 3k5 in accordance to DIN EN 60721-3-3.
The components must be mounted in suitable floor type cabinets using suitable fastening materials to ensure
that there is no mechanical tension.
The system may only be put into operation after being properly assembled.
Strong electrical / electromagnetic and mechanical influences must be avoided. This especially applies to the
installation of components and installation cables in the direct vicinity of fluorescent lamps or energy cables,
and to mounting on vibrating, unstable surfaces such as thin partition walls.
The system may not be installed in facilities or equipment that have damaging effects. Parts of the system may
be fed through such facilities or equipment, provided the requirements of the DIN VDE 0800 series of standards
are met.
For cabinet or wall installation, operating modules and visual displays should be installed between 800 mm
and 1800 mm above the place where the operator stands.
Danger – Electric shock!
Assembly and installation work may only be performed when the system is de-energised (voltage free).
ESD / EMC preventive measures
Before handling electronic modules, always take suitable precautions to prevent static electricity.
Protective and functional earth
For the device to function properly, the network side protective earthing (PE) connection must be
connected to the correct terminal. The functional earth (FE) must also be connected to the PE rail.
Neutral conductor
As a rule, it must be ensured that the neutral conductor is properly connected.
In particular, for three-phase connected devices in VARIODYN
protection must be provided against overvoltage caused by a break in the neutral conductor and
the phase shift which may result from this.
For single-phase connected devices, suitable protection against overcurrent must be ensured to
guard against the consequences of a break in the neutral conductor (usually caused by the
operator).
For more information, see Chapter 6.3.
Commissioning
A complete function test must be performed on the system upon completion of the commissioning
as well as after every change to the customer data programming.
6
®
D1 System
®
D1 cabinet systems, suitable
FB 798663.GB0 / 05.19