CH1 Range setting monitor (Resistance temperature detector type)
The value of resistance temperature detector type set in 'CH1 Range setting (Resistance temperature detector type)'
(Un\G598) can be checked. This description is specific to the RTD input module.
Monitor value
0
1
2
3
4
5
8
9
For channels where conversion is disabled, values stored in this area will not be updated because the input
range cannot be changed for these channels. For details, refer to the following.
Page 16 Input Range Setting Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Range setting monitor (Resistance
temperature detector type)
Range setting monitor (Resistance temperature detector type) [Q compatibility]
With the Q compatible mode function used, the value of resistance temperature detector type, which is set in the input range
setting, can be checked. This description is specific to the RTD input module.
b15
...
b12 b11
...
(1)
CH4
CH3
b15
...
b12 b11
...
(2)
CH8
CH7
(1) Range setting monitor (Resistance temperature detector type) (Un\G20) (setting range CH1 to CH4)
(2) Range setting monitor (Resistance temperature detector type) (Un\G21) (setting range CH5 to CH8)
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Range setting monitor (Resistance temperature
detector type)
The monitor values in the resistance temperature detector type setting are the same as those of R mode.
For channels where conversion is disabled, values stored in this area will not be updated because the input
range cannot be changed for these channels. For details, refer to the following.
Page 16 Input Range Setting Function
CH1
CH2
CH3
430
630
830
b8 b7
...
b4
b3
...
CH2
CH1
b8 b7
...
b4
b3
...
CH6
CH5
CH1
CH2
CH3
20
Description
Pt100 (-200 to 850)
Pt100 (-20 to 120)
JPt100 (-180 to 600)
JPt100 (-20 to 120)
Pt100 (0 to 200)
JPt100 (0 to 200)
Ni100 (-60 to 250)
Pt50 (-200 to 650)
CH4
CH5
1030
1230
b0
b0
CH4
CH5
21
Appendix 3 Buffer Memory Areas
CH6
CH7
CH8
1430
1630
1830
CH6
CH7
CH8
APPX
A
129