Thoroughly Flushing The Heating Installation ("Hot"); Checking Leak-Tightness; Checking The Heating Mode; Adapting The Unit To The Heating Installation - Vaillant ecoTEC plus VU Series Installation And Maintenance Instructions Manual

Hide thumbs Also See for ecoTEC plus VU Series:
Table of Contents

Advertisement

1
3.
Unscrew the cover from the flue gas analysis point (1).
4.
Measure the CO₂ content at the flue gas analysis point
(1).
5.
Compare the measured value with the corresponding
value in the table.
Checking the CO₂
content
CO₂ at full load
CO at full load
CO/CO₂
The value is OK.
The value is not OK; you cannot start up the
product.
Inform Customer Service.
9.11
Thoroughly flushing the heating installation
("hot")
1.
Operate the appliance until the boiler and the heating
system are up to temperature.
2.
Check the heating system for leaks.
3.
Connect a hose to the drain valve located at the lowest
position of the heating system.
4.
Shut off the boiler, open the drain valve and all purge
valves on the radiators and allow the water to flow out
of the heating system and the boiler quickly and fully.
5.
Close the drain valve.
6.
Fill the heating system again with water as described in
Filling the heating installation and Purging the heating
installation.
7.
Install the front casing.
9.12

Checking leak-tightness

Check the gas pipe, the heating circuit and the hot water
circuit for leak-tightness.
Check that the air/flue pipe has been installed correctly.
Condition: Room-sealed operation
Check whether the vacuum chamber has been closed
tightly.
30
Removed
Fitted front
front casing
casing
Natural gas H
Natural gas H
9.0 ±1.0 vol. %
9.2 ±1.0 vol. %
≤ 250 ppm
≤ 250 ppm
≤ 0.0031
≤ 0.0031
9.13

Checking the heating mode

1.
Activate the heating mode on the user interface.
2.
Turn all thermostatic valves on the radiators until they
are fully open.
3.
Allow the product to operate for at least 15 minutes.
4.
Purge the heating installation.
5.
Call up the Live Monitor.
Menu → Live Monitor
Status codes – Overview (→ Page 43)
If the product is working correctly, the display shows
S.04.
10 Adapting the unit to the heating
installation
You can reset/change the system parameters using the fol-
lowing menu items:
Menu → Installer level → Start inst. assistant
You can restart and run through the installation assistant at
any time.
Menu → Installer level Unit configuration
You can set/change the most important system parameters
in the Unit configuration menu item.
Menu → Installer level Diagnostics menu
You can set/change additional system parameters in the
Diagnostics menu item.
You can find an overview of all the system parameters in the
"Installer level – Overview" table in the appendix.
Installer level – Overview (→ Page 38)
10.1

Burner anti-cycling time

To prevent frequent switching on and off of the burner and
thus prevent energy losses, an electronic restart lockout
is activated for a specific period each time the burner is
switched off. The burner anti-cycling time is only active for
the heating mode. Domestic hot water mode during a burner
anti-cycling time does not affect the time function element.
10.1.1 Setting the burner anti-cycling time
Set the burner anti-cycling time via the diagnostics code.
Overview of diagnostics codes (→ Page 40)
T
Set maximum burner anti-cycling time [min]
Flow
(tar-
get)
1
5
[°C]
30
2.0
4.0
35
2.0
4.0
40
2.0
3.5
45
2.0
3.0
50
2.0
3.0
55
2.0
2.5
60
2.0
2.0
65
2.0
1.5
70
2.0
1.5
75
2.0
1.0
Installation and maintenance instructions ecoTEC plus 0020238195_07
10
15
20
25
30
8.5
12.5
16.5
20.5
25.0
7.5
11.0
15.0
18.5
22.0
6.5
10.0
13.0
16.5
19.5
6.0
8.5
11.5
14.0
17.0
5.0
7.5
9.5
12.0
14.0
4.5
6.0
8.0
10.0
11.5
3.5
5.0
6.0
7.5
9.0
2.5
3.5
4.5
5.5
6.5
2.0
2.5
2.5
3.0
3.5
1.0
1.0
1.0
1.0
1.0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents