Bradford White EVERHOT IGI-180C Series Installation And Operating Instruction Manual page 30

Tankless gas water heater for interior installation
Hide thumbs Also See for EVERHOT IGI-180C Series:
Table of Contents

Advertisement

GAS METER SIZE –NATURAL GAS ONLY
Be sure that the gas meter has sufficient capacity to supply the full rated gas input of the water heater as
well as the requirements of all other gas fired equipment supplied by the meter. If the gas meter is too
small, ask the gas company to install a larger meter having adequate capacity.
GAS PRESSURE REGULATION
Minimum and maximum gas supply pressures are listed below: The minimum gas pressure specified
below is required for the full input rating specified on the water heater rating plate.
Natural Gas:
Minimum: 6.0" w.c.
Maximum: 10.5" w.c.
BEFORE PLACING THE WATER HEATER IN OPERATION, CHECK FOR GAS LEAKAGE. USE SOAP
AND WATER SOLUTION OR OTHER MATERIAL ACCEPTABLE FOR THE PURPOSE OF LOCATING
GAS LEAKS.
DO NOT use matches, candles, flame or other sources of ignition for this purpose.
(Table assumes 0.3 inch pressure drop, specific gravity of 0.60 for gas pressures of 0.5 psi or less)
Pipe
Size in
10
20
Inches
(3)
(6)
¾"
278
190
1"
520
350
1 ¼"
1050
730
1 ½"
1600
1100
Note: After determining the length of pipe required, select the pipe size that will supply the cubic feet per
hour of gas required for the input rating of the gas appliances on the line.
The formula for figuring the cubic feet per hour required is:
The heating value may be obtained from the local natural gas utility
Capacity Table for LP Gas in MBH of undiluted liquefied petroleum gases
(Table assumes 11 inches of water column pressure at the inlet, 0.5" press. drop)
Pipe
Size in
10
20
Inches
(3)
(6)
½"
275
189
¾"
567
393
1 "
1071
732
1 1/4"
2205
1496
INITIAL OPERATION AND TESTING (INSTALLER ONLY)
1. Open the gas and water supply valves to the water heater.
2. Check for water and gas leaks. Use soap solution to check for gas leaks.
3. To check inlet supply pressure, remove the 1/8" NPT plug on the gas inlet supply fitting just below
the bottom casing and install a barb fitting for attaching a hose to a manometer. For checking the
gas manifold pressure, the plug is located just below the gas manifold connection inside the
control panel.
WARNING
Capacity Table for Natural Gas in Cubic Feet/Hour
Length of Pipe in Feet (Meters)
30
40
50
60
(9)
(12)
(15)
(18)
152
130
115
105
285
245
215
195
590
500
440
400
890
760
670
610
CFH = Gas Input of Appliance on the Line (Btu/hr)
Heating Value of Gas (Btu/Cu. Ft.)
Length of Pipe in Feet (Meters)
30
40
50
(9)
(12)
(15)
152
129
315
267
237
590
504
448
1212
1039
913
L.P. Gas:
Minimum: 10.0" w.c.
Maximum: 13.5" w.c.
70
80
90
100
(21)
(24)
(27)
(30)
96
90
84
79
180
170
160
150
370
350
320
305
560
530
490
460
60
70
80
(18)
(21)
(24)
217
196
185
409
378
346
834
771
724
30
125
150
175
(38)
(45)
(53)
72
64
59
130
120
110
275
250
225
410
380
350
90
100
125
150
(27)
(30)
(38)
(45)
173
162
146
322
307
275
252
677
630
567
511
200
(61)
55
100
210
320