Compressor Control - Fujitsu AS G07KGTA Series Service Instruction

Split type room air conditioner, wall mounted type inverter
Table of Contents

Advertisement

8. COMPRESSOR CONTROL

1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the Table 11.
(Table 11 : Compressor frequency range)
AO*G07KGCA
AO*G09KGCA
AO*G12KGCA
AO*G14KGCA
2. OPEARTION FREQUENCY CONTROL AT NORMAL START UP
The compressor frequency soon after the start-up is controlled as shown in the Fig.10
(Fig.10 : Compressor control at start-up)
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
(Frequency)
Frequency
Frequency
45rps
(Time)
Time
60sec
3. LIMITATION OF COMPRESSOR FREQUENCY BY OUTDOOR TEMPERATURE
The minimum compressor frequency is limited by outdoor temperature as shown in the Table12.
(Table12 : Limitation of Compressor Frequency)
[ Cooling/ Dry ]
AO*G07/ 09/ 12KGCA
AO*G14KGCA
[ Heating ]
AO*G07/ 09KGCA
AO*G12/ 14KGCA
Cooling / Dry
Minimum
Maximum
62rps
67rps
12rps
83rps
83rps
Time
Time
Frequency
Frequency
56rps
68rps
77rps
Time
Time
Time
140sec
170sec
220sec
38°C
Over
Under
20rps
---rps
20rps
---rps
19°C
Over
Under
1rps
1rps
1rps
1rps
Heating
Minimum
Maximum
12rps
110rps
Time
Time
Time
Frequency
Frequency
84rps
93rps
Time
Time
280sec
360sec
19°C
10°C
Over
Under
Over
---rps
20rps
5°C
0°C
Over
Under
Over
15rps
10rps
01-09
Time
Time
6
7
Frequency
103rps
Time
7
6
430sec
0°C
Under
Over
Under
28rps
36rps
28rps
36rps
-15°C
Under
Over
Under
36rps
37rps
17rps
25 rps