Greenheck Grease Trapper ESP Installation, Operation And Maintenance Manual page 18

Kitchen exhaust pollution control system
Table of Contents

Advertisement

Low Det Settings 1
Washes during low detergent
alarm: 0
Last wash on low det:
00:00:00am 00/00/00
Reset Det Count: OFF
Low Det Settings 2
Det Alm Delay: 15s
Wash Settings 3
ESP cell power supply
delay time after wash
cycle is aborted:
60 min
Test Wash Setup
Pre-Soak:
10 sec
Detergent:
10 sec
Soak:
10 sec
Rinse:
10 sec
Dry:
1 min
Drain:
10 sec
Start Test Wash?
NO
Wash Settings 4
Total Calculated Wash Time
(with Fan Dry):
176 min
C.
Service
d. BMS Configuration
BMS Configuration
Protocol::
BACnet MSTP
To adjust BACNET settings
press & hold ALARM &
ENTER keys to access BIOS
screens.
MODBUS SETUP
BMS Card
Address:
Baudrate
19200
18
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System
t
his sCrEEn allows UsEr to viEw low dEtErgEnt inFormation rECordEd with
.
wash systEm
Washes during low detergent alarm: Counts number of times wash cycle was
completed during a low detergent alarm.
Last wash on low detergent: Date and time stamp when last wash cycle was
stopped short OR prevented from starting.
Reset detergent count: Changing this from "OFF" to "ON" will change the count
for "Washes during low detergent alarm" back to 0.
t
his sCrEEn allows thE UsEr to adjUst thE dElay timE to initiatE a low
dEtErgEnt FaUlt aFtEr dEtECting no dEtErgEnt Flow
Default is 15 seconds.
t
his sCrEEn allows thE UsEr to adjUst thE dElay timE bEForE CElls Can bE
PowErEd again iF a wash CyClE is stoPPEd PrEmatUrEly
Default setting is 60 minutes.
t
his sCrEEn allows thE UsEr to adjUst sEttings For a Unit tEst wash and
also start a tEst wash
qUiCkly monitor a FUll wash sEqUEnCE
. d
a tEst wash
Uring a tEst wash
.
wash sEqUEnCE
t
his sCrEEn ProvidEs total CalCUlatEd wash timE From start oF wash Until
thE End oF thE Fan dry
to sChEdUlE thE wash CyClE to start
Can bE PErFormEd withoUt Cooking intErrUPtion
The BMS Configuration sub-menu allows the user to view and alter BMS protocol
settings. If the BMS protocol is BACnet or Modbus, additional screens allow
further configuration. See below for details. To access the BMS Configuration
sub-menu, enter the service password (Default=1000).
t
his sCrEEn allows thE UsEr to sElECt thE
ProtoCols rEqUirE a CommUniCations Card installEd in thE
,
Port
loCatEd on thE FaCE oF thE ControllEr
If the protocol is BACnet MSTP or BACnet IP/Eth, the user must enter into the
operating systems (BIOS) screens to adjust BACnet parameters.
t
his sCrEEn allows thE UsEr to adjUst
This screen only appears if the selected BMS protocol is set to Modbus.
The address is the Modbus address of the card installed in the SERIAL CARD port
1
located on the face of the controller. (Factory Default = 1).
The Baud Rate should be set to the BMS baud rate. (Factory Default = 19200).
. t
Est washEs allow For ExPEditEd sEqUEnCE timEs to
. C
hanging
,
PrEss thE baCk bUtton to abort thE tEst
. t
his Can bE UsEd as a hElPEr to dEtErminE what timE
,
to makE sUrE thE EntirE wash CyClE
bms
.
m
odbUs ParamEtErs
.
.
"no"
"yEs"
to
will start
.
. a
bms
ProtoCol
ll
sErial Card
.
®