Master Switch - Kohler 8.5RES Service Manual

Residential/commercial generator sets
Hide thumbs Also See for 8.5RES:
Table of Contents

Advertisement

1
8
7
6
1. Engine wiring harness connector plug (P1)
2. Continuous power mode jumper location (P7)
3. J15 connector
4. J16 connector
5. Generator set master switch
6. AUTO
7. VBAT
8. RUN
Figure 4-13 ADC 2100 (back cover removed)
Use the following procedure to disconnect the jumper, if
desired.
Procedure to disconnect the continuous power
mode jumper (optional).
Note: For most applications, it is not necessary to
disconnect the continuous power mode jumper.
1. Prevent the generator set from starting.
a. Move the generator set master switch to the
OFF/RESET position.
b. Disconnect power to the battery charger.
c. Disconnect the generator set engine starting
battery, negative (--) lead first.
2. Remove the controller from the generator set
housing.
TP-6196 5/04
2
5
4
3
a. Disconnect
connector P1 plug (35-pin) from the controller.
Disconnect the J15 and J16 connectors. See
Figure 4-13.
b. Remove the controller from the generator set
housing in order to access the back of the
controller.
3. Remove the controller's back cover to access the
jumper.
a. Note the labels on the three leads connected to
the
reconnection later. Disconnect the leads at the
pink connectors. See Figure 4-13.
b. Remove the cover screws and remove the
controller's back cover. See Figure 4-13.
4. Locate the P7 connector near the top of the
controller. See Figure 4-13. Remove the jumper
from pins 1 and 2 of the P7 connector. If the P7
connector has three pins, connect the jumper
across pins 2 and 3 for storage.
tp6196
5. Replace the controller's back cover and secure the
cover screws.
6. Reconnect the three pink connectors to the
generator set master switch as shown in
Figure 4-13.
7. Reconnect the J15 and J16 connectors.
8. Reconnect the generator set engine starting
battery, negative (--) lead last.
9. Reconnect power to the battery charger.
10. Place the generator set master switch in the AUTO
position.

4.7 Master Switch

The generator set master switch is a three-position
(RUN\OFF/RESET\AUTO) rocker switch. The leads
connecting to the master switch are labeled RUN, VBAT,
and AUTO. Check that the three pink connectors are
connected to the terminals on the back of the switch as
shown in Figure 4-13. Be careful not to reverse the RUN
and AUTO leads.
the
engine
wiring
generator
set
master
Section 4 Controller
harness
switch
for
33