Heating Start Up - Lennox LGA Series Unit Information

Hide thumbs Also See for LGA Series:
Table of Contents

Advertisement

TABLE 17
LGC/LCC Series 360 R410A − VAV
CIRCUIT 1
CIRCUIT 2
Outdoor
Coil En-
DIs
Suc
Dis
+10
+5
+10
tering Air
psig
psig
psig
Temp
65_F*
260
115
255
75_F
315
119
310
85_F
360
122
360
95_F
415
126
410
105_F
460
130
465
115_F
515
134
515
*Outdoor fans may cycle on and off at this temperature.
TABLE 18
LGA/LCA360H CAV with 3 compressors − R22
CIRCUIT 1
Outdoor
Coil En-
DIs
Suc
+10
+5
tering Air
psig
psig
Temp
65_F*
164
63
75_F
191
64
85_F
219
66
95_F
250
68
105_F
284
70
115_F
320
72
*Outdoor fans may cycle on and off at this temperature.
TABLE 19
LGA/LCA360H CAV with 3 compressors R410A
CIRCUIT 1
Outdoor
Coil En-
DIs
Suc
tering Air
+10
+5
psig
psig
Temp
65_F*
286
111
75_F
320
115
85_F
363
119
95_F
413
122
105_F
465
126
115_F
523
130
*Outdoor fans may cycle on and off at this temperature.
D−Charge Verification − Approach Method
1− Using the same thermometer, compare liquid temper-
ature to outdoor ambient temperature.
Approach Temperature = Liquid temperature minus
ambient temperature.
2− Approach temperature should match values in table
20. An approach temperature greater than value
shown indicates an undercharge. An approach tem-
perature less than value shown indicates an over-
charge.
3− Do not use the approach method if system pressures
do not match pressures in tables 6 through 19. The ap-
proach method is not valid for grossly over or under-
charged systems.
CIRCUIT 3
CIRCUIT 4
Suc
DIs
Suc
DIs
Suc
+5
+10
+5
+10
psig
psig
psig
psig
psig
122
270
124
280
123
125
330
127
330
126
129
380
130
390
129
132
430
133
440
133
136
480
136
490
136
139
535
139
550
140
CIRCUIT 2
CIRCUIT 3
Dis
Suc
DIs
Suc
+10
+5
+10
+5
psig
psig
psig
psig
176
76
178
75
207
77
206
76
233
78
234
77
270
80
271
78
303
81
301
79
346
82
345
81
CIRCUIT 2
CIRCUIT 3
Dis
Suc
DIs
Suc
+10
+5
+10
+5
psig
psig
psig
psig
307
125
302
123
351
130
336
129
397
132
382
133
448
135
430
137
501
137
478
140
561
142
534
141
Liquid Temp. Minus Ambient Temp.
Unit
1st Stage
248 R22
8°F+1
+5
CAV/VAV
(4.4°C+0.5)
248
R410A
8°F+1
CAV
(4.4°C+0.5)
248
R410A
7°F+1
VAV
(3.9°C+0.5)
300H
6°F+1
R22 CAV
(3.3°C+0.5)
300H
6°F+1
R22 VAV
(3.3°C+0.5)
300H
R410A
8°F+1
CAV
(4.4°C+0.5)
300H
5
R410A
°F+1
VAV
(2.8°C+0.5)
360
6°F+1
R22 CAV
(3.3°C+0.5)
360
8°F+1
R22 VAV
(4.4°C+0.5)
360
R410A
8°F+1
VAV
(4.4°C+0.5)
360
7°F+1
R410A
(3.9+0.5)
CAV
8°F + 1
360H
(4.4'°C +
R22
0.5)
12°F + 1
360H
(6.7°C +
R410A
0.5)
E−Heating Start Up
FOR YOUR SAFETY READ BEFORE LIGHTING
BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas
is heavier than air and will settle on the floor.
Use only your hand to push in or turn the gas control knob.
Never use tools. If the knob will not push in or turn by hand,
do not try to repair it, call a qualified service technician.
Force or attempted repair may result in a fire or explosion.
Electric shock hazard. Can cause
injury or death. Before attempting to
perform any service or maintenance,
turn the electrical power to unit OFF at
disconnect switch(es). Unit may have
multiple power supplies.
Page 55
TABLE 20
2nd Stage
3rd Stage
4th Stage
8°F+1
8°F+1
8°F+1
(4.4°C+0.5)
(4.4°C+0.5)
(4.4°C+0.5)
8°F+1
8°F+1
8°F+1
(4.4°C+0.5)
(4.4°C+0.5)
(4.4°C+0.5)
7°F+1
7°F+1
7°F+1
(3.9°C+0.5)
(3.9°C+0.5)
(3.9°C+0.5)
7°F+1
6°F+1
6°F+1
(3.9°C+0.5)
(3.3°C+0.5)
(3.3°C+0.5)
6°F+1
7°F+1
9°F+1
(3.3°C+0.5)
(3.9+0.5)
(5.0+0.5)
8°F+1
8°F+1
8°F+1
(4.4°C+0.5)
(4.4°C+0.5)
(4.4°C+0.5)
5
5
°F+1
°F+1
8°F+1
(2.8°C+0.5)
(2.8°C+0.5)
(4.4°C+0.5)
6°F+1
7°F+1
8°F+1
(3.3°C+0.5)
(3.9+0.5)
(4.4°C+0.5)
8°F+1
8°F+1
10°F+1
(4.4°C+0.5)
(4.4°C+0.5)
(5.6°C+0.5)
8°F+1
8°F+1
10°F+1
(4.4°C+0.5)
(4.4°C+0.5)
(5.6°C+0.5)
7°F+1
8°F+1
8°F+1
(3.9+0.5)
(4.4°C+0.5)
(4.4°C+0.5)
10°F + 1
8°F + 1
(5.6°C +
(4.4°C +
NA
0.5)
0.5)
14°F + 1
13°F + 1
(7.8°C +
(7.2°C +
NA
0.5)
0.5)